manualshive.com logo in svg
background image

E5CS-X

E5CS-X

38

J

ACCESSORIES (ORDER SEPARATELY)

Description

Part number

Protective cover

Hard plastic; protects front panel against dust, dirt and water drops

Y92A-48

Panel mounting adapter

Replacement for one supplied with each unit

Y92F-30

Specifications

Part number

E5CS-

j

1KJX

E5CS-

j

1PX

E5CS-

j

1GX

Sensor input type

Thermocouple
Type J (IC) and Type K (CA)

Platinum RTD (Pt: 100

)

DIN or JIS standard

Thermistor
(interchangeable type)

Supply voltage

100 to 240 VAC, 50/60 Hz; operates on 85 to 110% of rated voltage

Power consumption

Approx. 7 VA

Control

Contact

Type

SPDT relay

output

Max. load

3 A, 250 VAC (resistive load)

Voltage

Logic load

12 VDC, 20 mA with short-circuit protection

Hysteresis

0.2% of full scale during ON/OFF control action

Response

Output

2 seconds for output to change

time

Display

2 seconds for displayed indication to change

Service life

Mechanical

10 million operation minimum with contact output

Electrical

100,000 operations minimum with contact output

Alarm output

Type

SPST-NO relay

Max. load

1 A, 250 VAC (resistive load)

Setting range

Absolute value alarm:  Same as control output setting range
Others:  0 to full scale

Setting accuracy

Set value coincides with indicated value, so no relative error exists

Indication accuracy

±

0.5% of full scale, 

±

1 digit max.

Display range

–999 to 999 (limited to input type)

Control

Type

ON/OFF and PID with automatic tuning of proportional band, switch selectable

modes

Proportional band

3% to 20% (in PID mode) automatically adjusted according to the rise time of the 
controlled system

Reset time

4 minutes (in PID mode)

Rate time

0.4 minutes (in PID mode)

Proportional period

2 or 20 seconds, switch selectable

Sampling period

500 ms

Materials

Plastic case

Mounting

Fits 1/16 DIN panel cutout; includes panel mounting adapter

Connections

Screw terminals

Weight

170 g (6 oz.) without mounting adapter

Enclosure ratings

Front panel

IP50, NEMA 4 with optional Y92A-48N waterproof cover

Rear panel

IP30

Terminals

IP00

Approvals

UL

Recognized, File Number E68481

CSA

Certified, File Number LR59623

CE

Conforms to EN61010-1

Ambient temperature

Operating

–10

°

C to 55

°

C (14

°

F to 131

°

F)

Storage

–25

°

C to 65

°

C (–13

°

F to 149

°

F)

Humidity

35 to 85% RH

Insulation resistance

20 M

 minimum at 500 VDC

Dielectric strength

2,000 VAC, 50/60 Hz for 1 minute between current-carrying terminals of different polarity

Vibration

Mechanical durability

10 to 55 Hz, 0.75 mm (0.03 in) double amplitude in X, Y, and Z directions for 2 hours each

Malfunction durability

2 to 55 Hz, 2 G in X, Y, and Z directions for 10 minutes each

Shock

Mechanical durability

30 m/s

2

, in 6 directions, 3 times each

Malfunction durability

100 m/s

2

, in 6 directions, 3 times each

Содержание E5CS

Страница 1: ...D Pt 100 Ω DIN and JIS standards Interchangeable thermistor THE types Output Contact E5CS R1KJX F E5CS R1PX F E5CS R1GX F Voltage E5CS Q1KJX F E5CS Q1PX F E5CS Q1GX F Temperature Ranges Thermocouple Input Type Input type Type K Type J Temperature range 0 to 200 0 to 300 0 to 400 0 to 500 0 to 600 0 to 999 0 to 999 0 to 200 0 to 300 0 to 400 0 t0 500 Scale indication C C C F C F C F C F F C C C F C...

Страница 2: ...dication accuracy 0 5 of full scale 1 digit max Display range 999 to 999 limited to input type Control Type ON OFF and PID with automatic tuning of proportional band switch selectable modes Proportional band 3 to 20 in PID mode automatically adjusted according to the rise time of the controlled system Reset time 4 minutes in PID mode Rate time 0 4 minutes in PID mode Proportional period 2 or 20 se...

Страница 3: ... to OFF changes can be made simply by pressing the Up and Down keys 5 Down key decreases the set temperature or alarm value when pressed Decreases the value quickly when held down 8 Display data identifier lights SP when the set temperature is displayed on the main display and AL when an alarm value is displayed 6 Return key changes the value displayed on the main display each time pressed 9 Red d...

Страница 4: ...al mechanism Alarm mode selector switch Protection switch Right side view Control mode selector switch Left side view Temperature range selector switch Select the desired temperature range by using the temperature range selector switch rotary DIP type The other rotary DIP switch is used to select one of eight alarm functions Be sure the set temperature and alarm values are within the new range Oth...

Страница 5: ...l output ON OFF Set temperature Switch 1 OFF Temperature controller performs ON OFF action ON 1 6 5 4 3 2 P X ON Control output ON OFF Set temperature Switch 3 ON Used for cooling operations in ON OFF action ON 1 6 5 4 3 2 P X ON PID Action Set switch 1 of the function selector DIP switch to ON to perform PID control action Follow the steps described below Determining Proportional Period Set switc...

Страница 6: ...e main display Then set the shift value by using the Up or Down key Switch 4 ON Input shift function enabled ON 1 6 5 4 3 2 P X ON Fine adjustment of the temperature indication and the resulting controlled temperature is possible without changing or affecting the set point The input shift value can be set within the range from 99 9 to 99 F or C For ranges that have resolution to 0 1 the input shif...

Страница 7: ... 0 1 2 3 4 5 6 7 8 Temperature range 50 to 50 0 0 to 50 0 20 to 80 0 0 to 99 9 0 to 200 0 to 300 0 to 400 0 to 600 0 to 800 Scale indication C C C C F C F C C F F F Unit of measure 1 C or F 0 1 C or F 1 C or F 0 1 C or F 1 C or F Note 1 Do not set the selector switch to position 9 This will cause error message FFF or to be displayed 2 When changing scale ranges where the unit of measure changes 1 ...

Страница 8: ...dby sequence 6 Upper limit alarm with standby sequence 7 Lower limit alarm with standby sequence 8 Absolute value alarm Alarm value setting range Y must be within the temperature scale range Standby Sequence Alarm functions with standby sequence suppress nuisance alarms when the controller is first powered up As shown in the temperature charts at right the alarm output is suppressed until the temp...

Страница 9: ...ing heating reverse operation OFF during cooling normal operation fff blinks 1 Failure has occurred in thermocouple or platinum RTD 2 Temperature has risen much beyond scale range OFF blinks 1 Failure has occurred in platinum RTD 2 Polarities positive and negative of thermocouple are reversed 3 Temperature has fallen much below scale range OFF e11 or e33 1 Memory failure E11 display 2 Analog to di...

Страница 10: ...splashes of water or oil and high temperatures Separate the temperature controller from equipment that generates strong high frequency electrical noise such as welding equipment Sensor Input Connections The lead wires connecting the platinum RTD to the temperature controller must be separated from the power lines an the load lines wherever possible to prevent them from being inducted by electrical...

Отзывы: