E5CS-X

E5CS-X

42

Determining Control Output Operation

If the temperature controller is used to control a heater, the con-
trol output can be set to perform a reverse (inverted) operation.
Set switch 3 of the control output mode selector switch to OFF

Reverse

ON

output

OFF

Set temperature

Switch 3 OFF:
Controller performs reverse operation
used with heaters.

ON

1

6

5

4

3

2

P

X

ON

By contrast, if the temperature controller is used to control a
cooling device such as a chiller or freezer, set switch 3 to ON.

Normal ON
output

OFF

Set temperature

Switch 3 ON:
Controller performs normal operation for
cooling.

ON

1

6

5

4

3

2

P

X

ON

Auto-tuning of Proportional Band

Upon the initial power-up the proportional band is set to 3%. The
optimum proportional band width, however, is automatically
calculated and set within the range of 3 to 20%, according to the
changes in the temperature of the controlled system. This
automatic adjustment of the proportional band is performed
regardless of whether the controlled system is a heating or
cooling system.

When the power is turned OFF once, and the ON again, the con-
trol action starts with the previous proportional band. However,
the new proportional band is automatically calculated and set.

The calculation of the proportional band, however, is not carried
out if the temperature of the controlled system changes at a
faster rate than 7.5% of full scale per 2 seconds (e.g., faster then
3.75% per 

°

C per second with eh full scale of 100

°

C). In this

case, the previously calculated and set proportional band is used.

The temperature controller has an overshoot suppression
function that reduced second and subsequent overshoots to a
level less than the initial overshoot.

J

INPUT SHIFT FUNCTION

The temperature indication can be shifted by setting switch 4 of
the function selector DIP switch to ON, and pressing the mode
key repeatedly until the message “H0” (indicating ) input shift) is
displayed on the main display. Then set the shift value by using
the Up or Down key.

Switch 4 ON: Input shift function enabled.

ON

1

6

5

4

3

2

P

X

ON

Fine adjustment of the temperature indication and the resulting
controlled temperature is possible without changing or affecting
the set point.

The input shift value can be set within the range from –99.9 to 99
(

°

F or 

°

C).

For ranges that have resolution to 0.1, the input shift value can
be set within the range from –9.9 to 9.9 (

°

F or 

°

C. The input shift

function may be useful to make small temperature corrections to
the control system.

Note that the offset value remains effective even after switch 4
has been set to OFF. If the compensation action is not needed,
be sure to set the offset value to 0.

For example:

D

correction of known sensor calibration errors

D

correction of known steady temperature offset between the
heated work piece (load) and sensor. This is useful for
applications where the sensor cannot be located exactly at
the work piece.

D

alignment of temperature indications in a
multi-zone/multi-controller application, e.g., at ambient
temperature

Note that the input shift changes the value of the controlled
temperature when used in closed loop control. For example, with
a set point and indication of 100

°

C and input shift set at +10

°

C,

the controlled temperature will be 90

°

C.

Main 
display

Set input 
shift value

Temperature
measured by
sensor

Displayed
temperature

h 0

h 9

l 9

0 offset

offset by +9

°

offset by –9

°

100

°

C

100

°

C

100

°

C

100

°

C

109

°

C

91

°

C

J

MATCHING THE CONTROLLER TO 
SENSOR STANDARD

Use switch 5 of the function selector DIP switch to match the
controller to the thermocouple or RTD sensor to be used.

With switch 5 ON, the controller will accept DIN standard
sensors. With switch 5 OFF, the controller accepts JIS standard
sensors.

J

SELECTING SCALE INDICATION

Some dual-scale (

°

C/

°

F) temperature scale ranges may be

selected by rotary DIP switch. To specify the scale indication to
be displayed, used switch 6 on the in-line function selector DIP
switch.

With switch 6 set to ON, the controller displays Fahrenheit scale.
With switch 6 set to OFF, the controller displays Celsius scale.

Содержание E5CS

Страница 1: ...D Pt 100 Ω DIN and JIS standards Interchangeable thermistor THE types Output Contact E5CS R1KJX F E5CS R1PX F E5CS R1GX F Voltage E5CS Q1KJX F E5CS Q1PX F E5CS Q1GX F Temperature Ranges Thermocouple Input Type Input type Type K Type J Temperature range 0 to 200 0 to 300 0 to 400 0 to 500 0 to 600 0 to 999 0 to 999 0 to 200 0 to 300 0 to 400 0 t0 500 Scale indication C C C F C F C F C F F C C C F C...

Страница 2: ...dication accuracy 0 5 of full scale 1 digit max Display range 999 to 999 limited to input type Control Type ON OFF and PID with automatic tuning of proportional band switch selectable modes Proportional band 3 to 20 in PID mode automatically adjusted according to the rise time of the controlled system Reset time 4 minutes in PID mode Rate time 0 4 minutes in PID mode Proportional period 2 or 20 se...

Страница 3: ... to OFF changes can be made simply by pressing the Up and Down keys 5 Down key decreases the set temperature or alarm value when pressed Decreases the value quickly when held down 8 Display data identifier lights SP when the set temperature is displayed on the main display and AL when an alarm value is displayed 6 Return key changes the value displayed on the main display each time pressed 9 Red d...

Страница 4: ...al mechanism Alarm mode selector switch Protection switch Right side view Control mode selector switch Left side view Temperature range selector switch Select the desired temperature range by using the temperature range selector switch rotary DIP type The other rotary DIP switch is used to select one of eight alarm functions Be sure the set temperature and alarm values are within the new range Oth...

Страница 5: ...l output ON OFF Set temperature Switch 1 OFF Temperature controller performs ON OFF action ON 1 6 5 4 3 2 P X ON Control output ON OFF Set temperature Switch 3 ON Used for cooling operations in ON OFF action ON 1 6 5 4 3 2 P X ON PID Action Set switch 1 of the function selector DIP switch to ON to perform PID control action Follow the steps described below Determining Proportional Period Set switc...

Страница 6: ...e main display Then set the shift value by using the Up or Down key Switch 4 ON Input shift function enabled ON 1 6 5 4 3 2 P X ON Fine adjustment of the temperature indication and the resulting controlled temperature is possible without changing or affecting the set point The input shift value can be set within the range from 99 9 to 99 F or C For ranges that have resolution to 0 1 the input shif...

Страница 7: ... 0 1 2 3 4 5 6 7 8 Temperature range 50 to 50 0 0 to 50 0 20 to 80 0 0 to 99 9 0 to 200 0 to 300 0 to 400 0 to 600 0 to 800 Scale indication C C C C F C F C C F F F Unit of measure 1 C or F 0 1 C or F 1 C or F 0 1 C or F 1 C or F Note 1 Do not set the selector switch to position 9 This will cause error message FFF or to be displayed 2 When changing scale ranges where the unit of measure changes 1 ...

Страница 8: ...dby sequence 6 Upper limit alarm with standby sequence 7 Lower limit alarm with standby sequence 8 Absolute value alarm Alarm value setting range Y must be within the temperature scale range Standby Sequence Alarm functions with standby sequence suppress nuisance alarms when the controller is first powered up As shown in the temperature charts at right the alarm output is suppressed until the temp...

Страница 9: ...ing heating reverse operation OFF during cooling normal operation fff blinks 1 Failure has occurred in thermocouple or platinum RTD 2 Temperature has risen much beyond scale range OFF blinks 1 Failure has occurred in platinum RTD 2 Polarities positive and negative of thermocouple are reversed 3 Temperature has fallen much below scale range OFF e11 or e33 1 Memory failure E11 display 2 Analog to di...

Страница 10: ...splashes of water or oil and high temperatures Separate the temperature controller from equipment that generates strong high frequency electrical noise such as welding equipment Sensor Input Connections The lead wires connecting the platinum RTD to the temperature controller must be separated from the power lines an the load lines wherever possible to prevent them from being inducted by electrical...

Отзывы: