25
p
Proportional Band Setting
It is possible to set the proportional band within a range of 0.1 to 999.9
°
C/
°
F.
i
Integral Time Setting
It is possible to set the integral time within a range of 0 to 3999 s.
d
Derivative Time Setting
It is possible to set the derivative time within a range of 0 to 3999 s.
It is possible to set the necessary output value when the E5
J is in constant op-
eration within a range of 0.0% to 100.0%. The E5
J will be balanced with a devi-
ation between the set point and process value in P or PD control mode. This
deviation is called offset. The offset can be removed by changing the manual
reset value.
ofr
Manual Reset Value
Setting
Parameters on Display Level 1
Section 3-5