12
E5CJ
SP
OFF
ALL
Key protection
switch
PROTECT
Alarm mode selector 2
ALM2
ALM1
Alarm mode selector 1
INPUT
Input type selector
FUNCTION
Function selector
Top view
Bottom view
Note The E5CJ with no alarm does not incorporate ALM1 or ALM2.
2-3-2 Input Type Selector Setting
The input type selector is factory-set to 2 (K). Refer to the following table for the selection
of the desired sensor.
INPUT
Selector no.
Input
Set temperature range
Specified temperature range
°
C
°
F
°
C
°
F
0, 8
JPt100
–199.9 to 650.0
–199.9 to 999.9
–199.9 to 735.0
–199.9 to 999.9
1, 9
Pt100
–199.9 to 650.0
–199.9 to 999.9
–199.9 to 735.0
–199.9 to 999.9
2
K
–200 to 1300
–300 to 2300
–350 to 1450
–560 to 2560
3
J
–100 to 850
–100 to 1500
–195 to 945
–260 to 1660
4
T
–199.9 to 400.0
–199.9 to 700.0
–199.9 to 460.0
–199.9 to 790.0
5
L
–100 to 850
–100 to 1500
–195 to 945
–260 to 1660
6
U
–199.9 to 400.0
–199.9 to 700.0
–199.9 to 460.0
–199.9 to 790.0
7
N
–200 to 1300
–300 to 2300
–350 to 1450
–560 to 2560
Note The resistance of the JPt100 at a temperature of 100
°
C is 139.16
Ω
and that of
the Pt100 at a temperature of 100
°
C is 138.50
Ω
.
1, 2, 3...
1. To use Fahrenheit, set function selector 4 to ON, which is usually set to OFF.
2. Insert the internal mechanism into the case.
3. Turn on the E5
J so that
d-u
will be displayed on the process value display.
Then press the Up Key so that
f
will be displayed on the set value display.
4. Turn off the power in two seconds.
5. Draw the internal mechanism from the case and set function selector 4 to
OFF and turn on the E5
J.
Internal Switch Settings
Section 2-3