5
Item
Specification
Indication method
E5AJ
All digital indication (PV: Red, 15 mm; SV: Green,
10.5 mm)
E5EJ
All digital indication (PV: Red, 14 mm; SV: Green,
9.5 mm)
E5CJ
All digital indication (PV: Red, 12 mm, SV: Green 8.0
mm)
Event input
Contact input: ON: 1 k
Ω
max. OFF: 100 k
Ω
min.
No-contact input: ON: residual voltage of 3 V max; OFF:
current leakage of 1 mA max.
Other function
•
Key protect
•
Cooling operation/Heating operation
•
Heater burnout alarm
Model with event input (E5
J-
B)
•
Set point selection (set point x 2)
•
RUN/STOP (E5AJ-
B and E5EJ-
B only)
Ambient operating temperature
–10
°
C to 55
°
C (with no condensation)
Ambient operating humidity
35 to 85%
Storage temperature
–25
°
C to 65
°
C (with no condensation)
Model
Specification
E53-R Relay Output Unit
SPDT (SPST-NO when used with the
E5
J), 5 A at 250 VAC (resistive load)
E53-Q Voltage Output Unit
NPN, 40 mA at 12 VDC (with
short-circuit protection)
E53-Q3 Voltage Output Unit
NPN, 20 mA at 24 VDC (with
short-circuit protection)
E53-Q4 Voltage Output Unit
PNP, 20 mA at 24 VDC (with
short-circuit protection)
E53-C3 Linear Output Unit
4 to 20 mA DC with a load of 600
Ω
max. (with a resolution of approximately
2600 when used with the E5
J) (see
note)
E53-C3D Linear Output Unit
0 to 20 mA DC with a load of 600
Ω
max. (with a resolution of approximately
2600 when used with the E5
J)
E53-V34 Linear Output Unit
0 to 10 VDC with a load of 1 k
Ω
min.
(with a resolution of approximately 2600
when used with the E5
J)
E53-V35 Linear Output Unit
0 to 5 VDC with a load of 1 k
Ω
min.
(with a resolution of approximately 2600
when used with the E5
J)
Note The E53-C cannot be used.
Item
Specification
Maximum continuous heater current
50 A
Dielectric strength
1,000 VAC
Vibration resistance
50 Hz, approx. 98 m/s
2
(10G)
Weight
E54-CT1: Approx. 11.5 g
E54-CT3: Approx. 50 g
Output Units
Current Transformer (CT)
Specifications
Section 1-3