20
3-3
List of Parameters
Display Level 0
Display
Name
Setting range
Setting
before
shipping
Remarks
---
Process value
display and set
point setting
Set point lower limit
to set point upper
limit (
°
C/
°
F)
0
The present set point is
displayed and can be
changed if the E5
J
incorporates an event input
function
AL-1
Alarm set value 1
–1999 to 9999
°
C/
°
F
The decimal position
varies with the kind
of input.
0
Not displayed if alarm mode
switch 1 is set to 0.
AL-2
Alarm set value 2
–1999 to 9999
°
C/
°
F
The decimal position
varies with the kind
of input.
0
Not displayed if alarm mode
switch 2 is set to 0.
To go to the next level, press the Level Key for 1 s min.
Note The values shown in Fahrenheit are applicable only for E5
J-
-F Mod-
els.
Display Level 1
Display
Name
Setting/Display
Range
Setting
before
shipping
Remarks
0
Output value
display
0.0 to 100.0 %
CP
Control period
1 to 99 s
20
Displayed and can be set if
the E5
J in PID control
operation has relay control
output or voltage control
output.
HYS
Hysteresis
0.1 to 999.9
°
C/
°
F
1.0 (1.8)
Displayed and can be set
when the E5
J is in ON/OFF
control operation.
SP-0
Set point 0
Set point lower limit
to set point upper
limit (
°
C/
°
F)
0
For models incorporating an
event input function.
SP-1
Set point 1
Set point lower limit
to set point upper
limit (
°
C/
°
F)
0
For models incorporating an
event input function.
SP-2
Set point 2
Set point lower limit
to set point upper
limit (
°
C/
°
F)
0
For models incorporating an
event input 2 function.
Displayed and can be set if
the default value is changed
on the engineering level.
SP-3
Set point 3
Set point lower limit
to set point upper
limit (
°
C/
°
F)
0
For models incorporating an
event input 2 function.
Displayed and can be set if
the default value is changed
on the engineering level.
in-S
Input shift value
–199.9 to 999.9
°
C/
°
F
0.0
Displayed and can be set if
the default value is changed
on the engineering level.
List of Parameters
Section 3-3