Program Mode
Pattern number
Synchronized with with the pattern
number of level 0 mode.
Step number
Changed to the ramp setting method. Refer to the
Operation Manual for the ramp setting method.
Time setting method
Target SP 0
Step 0 SP
Ramp Rate 0
Step 0 time
Soak time 0
Target SP 7
Step 7 SP
Ramp rate 7
Step 7 time
(see note)
Soak time 7 (max.)
Time Setting Method
Set the number of steps to be used beginning with step 0 (e.g., step
0 SP, step 0 time, step 1 SP, and step 1 time).
The step target value can be set within a range between the
lower and upper target value limits. The default value is zero.
The step time can be set within a range between 0.00 and 99.59
(in hr and min or min and s). The default value is 0.00.
Step 0
Step 1
Step 3
Step 2
Step 0 time
Step 1 time
Step 2 time
Step 3 time
A: Step 0 and step 3 SP
B: Step 1 and step 2 SP
Time
Step 0 is flat as shown in the above graph. Set step 0 to 0.00 so that
step 1 will be the actual first step when writing ramp-start programs.
Note:
Up to step 15 (i.e., a total of 16 steps) can
be set in the time setting method.
Time signal 1 enabled step
Time signal 1 ON time
Time signal 1 OFF time
Time signal 2 enabled step
Time signal 2 ON time
Time signal 2 OFF time
Time Signal
Two types of time signal patterns can be set in each pattern.
Time signal output
ON time
Time
OFF time
Two types of time signal timers are available (i.e., ON-time and OFF-time use), each
of which starts with the edge of the step.
The output is ON from the moment the ON time elapses until the OFF time elapses.
Set the step so that the time signal is triggered by the time signal 1/2 enabled step
parameters. The default is step 0.
Set the ON/OFF timing with the timing signal 1/2 ON-time and time signal 1/2
OFF-time parameters in Program mode.
ON Conditions
If the ON time is shorter than the OFF time, the signal will be reset or ON after the ON
time elapses until the next pattern starts.
The signal is not ON if there is no difference in period between the ON time and OFF time.
If ADVANCE is executed while the time signal setting step is executed, the time equiv-
alent to the setting step will be deemed to have elapsed. In the above graph, for exam-
ple, the signal is ON from the edge of the next step until the OFF time elapses.
Pattern execution count
Alarm value 1 (displayed only if the alarm is allocated.)
Alarm value 2 (displayed only if the alarm is allocated.)
Alarm value 3 (displayed only if the alarm is allocated.)