Control and Status area
Section 4-3
64
IR n+3.00,
IR n+3.01
CANopen state
These two bits indicate the CANopen state of the C200HW-
CORT21-V1.
IR n+3.01
IR n+3.00
CANopen state
0
0
Not active.
CANopen is not active when:
•
Initialisation is not finished yet.
•
Unit has gone 'Bus Off' due to non-
recoverable errors detected on the
CANopen network.
•
IR n.00 is not set.
0
1
Pre-Operational
This state is entered autonomously after
initialisation or after Bus Off recovery, and
after receiving the NMT
command
'Enter_Pre-Operational_State’.
The Unit is accessible via SDOs to allow
configuration.
1
0
Operational
This state is entered after receiving
the NMT command ‘Start_Remote_Node’.
The Unit is fully operational and can be
accessed via SDOs and PDOs.
1
1
Stopped
This state is entered after receiving the
NMT command ‘Stop_Remote_Node’
In this state all data communication (via
SDOs as well as PDOs) is disabled.
Refer to section 1-3-4-1 for more details about the CANopen
state machine.
15 14 13 12 11 10 9
8
7
6
5
4
3
2
1
0
IR n+5
Emergency trigger
Error count
15 14 13 12 11 10 9
8
7
6
5
4
3
2
1
0
IR n+6
Application Object 2100h, 01h
Application Object 2100h, 02h
15 14 13 12 11 10 9
8
7
6
5
4
3
2
1
0
IR n+7
Application Object 2100h, 03h
Application Object 2100h, 04h
Содержание C200HW-CORT21-V1
Страница 2: ...C200HW CORT21 V1 CANopen Slave Unit OPERATION MANUAL OMRON Cat No W904 E2 2 ...
Страница 3: ......
Страница 4: ......
Страница 5: ......
Страница 6: ...C200HW CORT21 V1 CANopen Slave Unit Operation Manual Produced June 2001 ...
Страница 7: ...iv ...
Страница 9: ...vi ...
Страница 13: ...x ...
Страница 47: ...Performance Section 2 3 30 ...
Страница 85: ...Control and Status area Section 4 3 68 ...
Страница 113: ...Flow diagrams Section 6 6 96 ...
Страница 123: ...Maintenance Section 7 3 106 ...
Страница 133: ...116 ...
Страница 135: ...118 ...
Страница 139: ...122 ...
Страница 141: ......