249
Troubleshooting
Section 9-2
Note
“Ctrl+X Keys” means to press the X Key while holding down the Ctrl Key.
ERR (error) indicator is flashing.
(Battery error)
The battery connector is disconnected. Connect the battery connector
properly.
The battery voltage has dropped.
Replace with new battery.
All ERR indicators are flashing and
PROGRAM MEMORY ERROR
appears on the initial screen, and
pressing Ctrl+X Keys is ineffective.
The BASIC program memory is
destroyed.
Change the DM setting so that the
flash ROM is not read automatically at
startup and then toggle the START/
STOP switch on the front panel of the
Unit to START, STOP, and START
again. The BASIC program memory
will be cleared.
If the program is backed up in flash
ROM, the program memory can be
recovered afterwards using the
ROMLOAD command.
Error
Probable cause
Possible correction