7 Troubleshooting
7 Troubleshooting
Perform the checks shown below if the unit is operating abnormally.
If the unit continues to operate abnormally, please contact our Electronic Systems &
Equipments Customer Support Center.
Problem
Check and remedy
The LED does not appear when
the AC input is connected to
commercial power and the
“Power” switch is turned ON.
1. Make sure the AC input is securely connected to commercial power.
2. AC input overcurrent protection is activated and power is cut.
●
If the black INPUT PROTECTION button pops up, there are too many connected devices
or there was a short-circuit with the connected devices. Disconnect all the connected devices,
press the black INPUT PROTECTION switch (overcurrent protection switch), and turn on the
“Power” switch.
●
If the status indicator does not display properly after you perform the above operation,
there is a problem with the unit.
(See “3-4 Interpreting beeps and displays”.)
Backup is not possible. The
computer stops when a power
failure occurs.
The battery may not be fully charged.
Perform the test after charging the battery for at least 8 hours. The battery can be charged just
by connecting the AC input to a wall outlet. The “Power” switch can be either ON or OFF.
Backup is performed too
frequently.
Frequent switching is performed
although a power failure does
not occur.
You hear the sound of switching.
Variations (decrease) in the input power occur frequently. Or, noise may be included that
significantly distorts the voltage waveform of the input power.
●
Try and check what happens when connecting the unit to a different wall outlet
(commercial power) located some distance away from the device consuming a large amount
of power.
●
This problem may occur also when you connect many devices to a plug strip or extension
cord connected to the UPS if it is a long or thin cable.
Does not turn ON when “Power”
switch is pressed.
The unit does not start up when the input power supply voltage/frequency is abnormal. (The
status indicator displays “H-”, “-H”, “L-”, “-L”, “HH” or “LL”.) Check the voltage and frequency of
the input power supply.
See also “3-4 Interpreting beeps and displays”,
The display is abnormal.
●
The display is unstable.
●
White lines occur.
●
Noise increases.
The probable cause is noise that occurs inside the UPS.
●
Ground all devices connected to the UPS. Connect them to a wall outlet (commercial
power) for 3-pin plugs or connect their Grounding Terminal to the Grounding Terminal of a wall
outlet.
●
This problem may occur when power cords are long or placed closely or when the UPS
and devices to be backed up are placed closely. Rearrange them.
●
If the UPS or devices connected to the UPS are contained in a metal rack, attempt to
ground the rack itself.
The battery replacement lamp
lights up or blinks, and the
beeper sounds at 2-second
intervals.
●
When the battery replacement lamp blinks: Judged as battery deterioration by
self-diagnosis test. Replace the battery as only the short backup operation time is available.
See also ”4-1-2 Self-diagnosis test”
●
When the battery replacement lamp is ON: Battery life counter went off-scale. The life of
the battery has expired. Replace the battery.
See also ”4-2-1 Notification that the battery needs to be replaced”.
The status indicator shows
“
”, and the beeper sounds at
0.5-second intervals.
There are too many connected devices. Reduce the number of connected devices until “
” is
displayed on the status indicator.
The status indicator blinks
“
”,
and the beeper sounds
continuously
Output stopped due to exceeded connection capacity.
Turn OFF all power to the unit and connected devices, and reduce the number of connected
devices. Then, turn the power to the unit and connected devices back ON and check whether
"
" is displayed on the status indicator. See also “3-4 Interpreting beeps and displays”,
BA75T/BA100T/BA100R
85
7
Содержание BA100R
Страница 23: ...2 Installation and connection 2 1 Installation Incorrect Positions BA75T BA100T BA100R 22...
Страница 87: ...8 Note of Chinese 8 Note of Chinese UPS UPS 1 UPS FA OA Windows BA75T BA100T BA100R 86...
Страница 88: ...8 Note of Chinese 2 FA OA A VCCI A BA75T BA100T 12 5 BA100R 13 BA75T BA100T BA100R 87 8...
Страница 89: ...8 Note of Chinese AC AC100V 110V 115V 120V 50 60Hz AC UPS 10 90 0 C 40 C 25 85 BA75T BA100T BA100R 88...
Страница 90: ...8 Note of Chinese 5cm AC 25 5 30 4 AC AC AC AC BA75T BA100T BA100R 89 8...
Страница 91: ...8 Note of Chinese ON OFF AC INPUT PROTECTION 1mA AC UPS AC UPS BA75T BA100T BA100R 90...
Страница 92: ...8 Note of Chinese BA75T BA100T BA100R 91 8...
Страница 93: ...8 Note of Chinese AC UPS 25 25 6 40 2 AC AC DC250V BA75T BA100T BA100R 92...
Страница 94: ...8 Note of Chinese UPS 100V http www fa omron com cn AC AC 50 60Hz 3 3 3 Pb BA75T BA100T BA100R 93 8...
Страница 97: ...9 References 9 2 Dimensions 9 2 Dimensions Unit mm Tolerance 2mm BA75T BA100T BA100R BA75T BA100T BA100R 96...
Страница 98: ...9 References 9 2 Dimensions Unit mm Tolerance 1mm Upright stand for BA75T 100T BAP100T BA75T BA100T BA100R 97 9...
Страница 99: ...9 References 9 2 Dimensions Upright stand for BA100R BAP100R BA75T BA100T BA100R 98...
Страница 100: ...9 References 9 2 Dimensions Rubber feet BA75T BA100T BA100R 99 9...
Страница 101: ...9 References 9 2 Dimensions Using Ear brackets BAP100RS BA75T BA100T BA100R 100...
Страница 103: ...9 References 9 4 China RoHS Information 9 4 China RoHS Information BA75T BA100T BA100R 102...