3 Check and start operation
3-4 Interpreting beeps and displays
No.
Status
indicator
Power
supply
output
lamp
Battery
mode
lamp
Battery
replace
ment
lamp
Beep
Charging
Description
Solution
15
None
(ON)
AC input voltage is too
low.
Use within the AC input
voltage/frequency range
described in the
specifications.
16
None
(ON)
AC input voltage is too
high and AC input
frequency is too low.
17
None
(ON)
AC input frequency is
too low.
18
None
(ON)
AC input voltage and
AC input frequency are
both too low.
3-4-4 Displays and beeps when there is an equipment
failure
(1) When "Power" switch is "ON"
19
Intermittent
0.5-second
intervals
ON
Discharging
There are too many
connected devices and
the rated capacity is
exceeded. If this state
continues for as long as
or longer than the times
described below,
commercial power
continues to be supplied
through bypass
operation (Note 1)
・
When connection
capacity is at 110% or
higher: Bypass
operation begins
promptly.
Reduce the number of
connected devices until
the display appears as
in status No. 4
20
blinking
bypass
Intermittent
0.5-second
intervals
ON
Discharging
21
OFF
OFF
Battery charge stopped
because the battery
ambient temperature of
40°C or higher was
detected.
Lower the ambient
temperature to less than
40°C.
22
Continuous
---
(Note 2)
Output stopped due to
exceeded connection
capacity.
Turn OFF the power
switches of all devices
connected to the unit
reduce the number of
connected devices, and
turn the “Power” switch
back ON again.
23
Continuous
---
(Note 2)
Check that the
connection capacity has
not exceeded the rated
capacity.
Check that the AC input
of connected devices is
not short-circuited, or
that the connection
capacity does not
exceed the rated
capacity.
BA75T/BA100T/BA100R
48
Содержание BA100R
Страница 23: ...2 Installation and connection 2 1 Installation Incorrect Positions BA75T BA100T BA100R 22...
Страница 87: ...8 Note of Chinese 8 Note of Chinese UPS UPS 1 UPS FA OA Windows BA75T BA100T BA100R 86...
Страница 88: ...8 Note of Chinese 2 FA OA A VCCI A BA75T BA100T 12 5 BA100R 13 BA75T BA100T BA100R 87 8...
Страница 89: ...8 Note of Chinese AC AC100V 110V 115V 120V 50 60Hz AC UPS 10 90 0 C 40 C 25 85 BA75T BA100T BA100R 88...
Страница 90: ...8 Note of Chinese 5cm AC 25 5 30 4 AC AC AC AC BA75T BA100T BA100R 89 8...
Страница 91: ...8 Note of Chinese ON OFF AC INPUT PROTECTION 1mA AC UPS AC UPS BA75T BA100T BA100R 90...
Страница 92: ...8 Note of Chinese BA75T BA100T BA100R 91 8...
Страница 93: ...8 Note of Chinese AC UPS 25 25 6 40 2 AC AC DC250V BA75T BA100T BA100R 92...
Страница 94: ...8 Note of Chinese UPS 100V http www fa omron com cn AC AC 50 60Hz 3 3 3 Pb BA75T BA100T BA100R 93 8...
Страница 97: ...9 References 9 2 Dimensions 9 2 Dimensions Unit mm Tolerance 2mm BA75T BA100T BA100R BA75T BA100T BA100R 96...
Страница 98: ...9 References 9 2 Dimensions Unit mm Tolerance 1mm Upright stand for BA75T 100T BAP100T BA75T BA100T BA100R 97 9...
Страница 99: ...9 References 9 2 Dimensions Upright stand for BA100R BAP100R BA75T BA100T BA100R 98...
Страница 100: ...9 References 9 2 Dimensions Rubber feet BA75T BA100T BA100R 99 9...
Страница 101: ...9 References 9 2 Dimensions Using Ear brackets BAP100RS BA75T BA100T BA100R 100...
Страница 103: ...9 References 9 4 China RoHS Information 9 4 China RoHS Information BA75T BA100T BA100R 102...