Main circuit
400V class
• At inverter ND rating setting
• At inverter LD/VLD rating setting
Note
1.
The models described in the table are examples of selection. When using the device, choose a model that has appropriate
breaking capacity and sensitive current by taking short circuit current and relevant laws and regulations into consideration
based on the rated current shown in the table.
2.
The applicable motor capacity is a selection example when standard motors 4-pole motor model 60HZ 200VAC (200V class)
is used.
3.
The electric durability ensured when the magnetic contactor is used in AC-1 class is 500,000 times, while emergency stop
during motor operation is 25 times.
4.
If there is emergency stop during motor drive or commercial operation is performed, choose the magnetic contactor on the
motor side in AC-3 class against the rated current of motor.
5.
If the rated capacity of inverter is larger than the motor capacity, choose instruments based on the inverter model.
Model
3G3RX2
Applicable
motor
(kW)
Applicable instrument (input voltage 200 to 220V)
Without power factor improvement reactor
With power factor improvement reactor
(3G3AX-AL or 3G3AX-DL)
Earth-leakage breaker
(ELB)
Magnetic contactor
(MC)
Earth-leakage breaker
(ELB)
Magnetic contactor
(MC)
Example
of model
Rated
current
AC-1
AC-3
Example
of model
Rated
current
AC-1
AC-3
A4007
0.75
EX50C
5
HS8
HS8
EX50C
5
HS8
HS8
A4015
1.5
EX50C
10
HS8
HS8
EX50C
5
HS8
HS8
A4022
2.2
EX50C
10
HS8
HS8
EX50C
10
HS8
HS8
A4037
3.7
EXK50-C
15
HS8
HS10
EX50C
10
HS8
HS8
A4055
5.5
EXK50-C
20
HS8
HS20
EXK50-C
15
HS8
HS20
A4075
7.5
EXK50-C
30
HS8
HS25
EXK50-C
20
HS8
HS20
A4110
11
EXK50-C
40
HS20
HS35
EXK50-C
30
HS8
HS25
A4150
15
EXK50-C
50
HS25
HS50
EXK50-C
40
HS20
HS35
A4185
18.5
EXK100-C
75
HS35
HS50
EXK50-C
50
HS20
HS35
A4220
22
EXK100-C
75
HS50
H65C
EXK60-C
60
HS35
HS50
A4300
30
EXK100-C
100
HS50
H80C
EXK100-C
75
HS50
H65C
A4370
37
RXK125-S
125
H80C
H100C
EXK100-C
100
HS50
H65C
A4450
45
EXK225
150
H80C
H125C
RXK125-S
125
H65C
H80C
A4550
55
EXK225
200
H100C
H125C
EXK225
150
H80C
H100C
B4750
75
RXK250-S
250
H150C
H200C
EXK225
200
H100C
H125C
B4900
90
EX400
300
H200C
H250C
EXK225
225
H125C
H150C
B411K
110
EX400
400
H200C
H300C
EX400
300
H150C
H250C
B413K
132
EX600B
500
H250C
H300C
EX400
350
H200C
H250C
Model
3G3RX2
Applicable
motor
(kW)
Applicable instrument (input voltage 200 to 220V)
Without power factor improvement reactor
With power factor improvement reactor
(3G3AX-AL or 3G3AX-DL)
Earth-leakage breaker
(ELB)
Magnetic contactor
(MC)
Earth-leakage breaker
(ELB)
Magnetic contactor
(MC)
Example
of model
Rated
current
AC-1
AC-3
Example
of model
Rated
current
AC-1
AC-3
A4007
1.5
EX50C
10
HS8
HS8
EX50C
5
HS8
HS8
A4015
2.2
EX50C
10
HS8
HS8
EX50C
10
HS8
HS8
A4022
3.7
EXK50-C
15
HS8
HS10
EX50C
10
HS8
HS8
A4037
5.5
EXK50-C
20
HS8
HS20
EXK50-C
15
HS8
HS20
A4055
7.5
EXK50-C
30
HS8
HS25
EXK50-C
20
HS8
HS20
A4075
11
EXK50-C
40
HS20
HS35
EXK50-C
30
HS8
HS25
A4110
15
EXK50-C
50
HS25
HS50
EXK50-C
40
HS20
HS35
A4150
18.5
EXK100-C
75
HS35
HS50
EXK50-C
50
HS20
HS35
A4185
22
EXK100-C
75
HS50
H65C
EXK60-C
60
HS35
HS50
A4220
30
EXK100-C
100
HS50
H80C
EXK100-C
75
HS50
H65C
A4300
37
RXK125-S
125
H80C
H100C
EXK100-C
100
HS50
H65C
A4370
45
EXK225
150
H80C
H125C
RXK125-S
125
H65C
H80C
A4450
55
EXK225
200
H100C
H125C
EXK225
150
H80C
H100C
A4550
75
EX400
250
H150C
H200C
EXK225
200
H100C
H125C
B4750
90
EX400
300
H200C
H250C
EXK225
225
H125C
H150C
B4900
110
EX400
400
H200C
H300C
EX400
300
H150C
H250C
B411K
132
EX600B
500
H250C
H300C
EX400
350
H200C
H250C
B413K
160
EX600B
600
H400C
H400C
EX400
400
H250C
H300C