Battery Power
Here you can set the amount of time you want the backlighting to stay on when
activated and the unit is running on battery power only.
You can not set the backlighting to be “Always On” when the
unit is powered by battery power.
When set to 10 or 30 seconds the backlight will come on and then turn off after
the allotted time has expired. If backlighting is not required it is recommended
that you select “Always Off” to preserve battery life.
(2) Sensor Options
Sample Interval
Here you can set how oftern the device samples the sensor and updates the LCD.
The sample interval is always fixed at 0.382 seconds/sample
(2.6 samples/second) when powered externally, regardless of
the setting in the Configuration Wizard. The purpose of the
sample interval setting is for conserving battery life, not for
display damping or averaging, and therefore has no effect
unless operating on battery power only.
RTD Alpha
Select the proper curve for the sensor or probe you will be measuring with your unit.
If you ordered a unit with an integral probe, this setting will
be factory locked to match the probe installed.
(3) Front Panel Options
Show Decimal Point
Select this option to turn on or off the last digit and decimal point
Disable Bar Graph
Select this option to remove the bar graph indicator from the display.
(4) Alarm Output
Alarm On
Disabled - The alarm output is disabled and will not operate.
Rising - The alarm output activates ONLY when the temperature meets or
exceeds the High Setpoint.
Falling - The alarm output activates ONLY when the temperature meets or falls
below the Low Setpoint.
Setup & Configuration
4
4-9
NOTE:
NOTE:
NOTE: