46 -
DP400S - User manual
71 Alarm threshold
Select setpoint for alarm 2
-999999..+999999
[Digit
2
],
Default
: 0.0.
72 Deviation threshold
Select deviation value from alarm 2 setpoint for the band alarm
0..+999999
[Digit
2
],
Default
: 0.0.
73 Hysteresis
Alarm 2 hysteresis
-10000..+10000
[Digit
2
],
Default
: 0.0.
74 Reset type
Alarm 2 contact reset type
Automatic
(
Default
)
Manual
Manual reset by keyboard
Manual stored
Keeps relay status also after an eventual power failure
75 Error contact
State of contact for alarm 2 output in case of error
Open (
Default
)
Closed
77 Actuation delay
Alarm 2 delay.
-3600..+3600
s.
Default
: 0
Negative: delay in alarm exit phase.
Positive: delay in alarm entry phase.
78 Lower limit
Lower limit for alarm 2 setpoint
-999999..+999999
[Digit
2
].
Default
: 0.