44 -
DP400S - User manual
55 Contact type
Select the alarm 1 output contact and intervention type
Normally open (
Default
)
N.O. - Disabled at starting
Normally closed
N.C. - Disabled at starting
56 Alarm threshold
Select setpoint for alarm 1
-999999..+999999
[Digit
2
],
Default
: 0.0.
57 Deviation threshold
Select deviation value from alarm 1 setpoint for the band alarm
0..+999999
[Digit
2
],
Default
: 0.0.
58 Hysteresis
Alarm 1 hysteresis
-10000..+10000
[Digit
2
],
Default
: 0.0.
59 Reset type
Alarm 1 contact reset type
Automatic (
Default
)
Manual
Manual reset by keyboard
Manual stored
Keeps relay status also after an eventual power failure
60 Error contact
State of contact for alarm 1 output in case of error
Open (
Default
)
Closed
62 Actuation delay
Alarm 1 delay.
-3600..+3600
seconds.
Default
: 0
Negative: delay in alarm exit phase.
Positive: delay in alarm entry phase.