16
negative value allow ed is -199.9, -19.99, or -1.999.
Note:
Note:
Note:
Note:
Note: InPC is reset to zero when
the input type is changed, or when decimal position is changed in T/C or RT D
ranges.
Changing decimal position in current or voltage ranges will not reset InPC.
FiLt
FiLt
FiLt
FiLt
FiLt
Digital Filter: Select OFF
OFF
OFF
OFF
OFF, 1
1
1
1
1 to 99
99
99
99
99. In some cases the time constant of the sensor,
or noise could cause the display to jump enough to be unreadabl
e.
A setting of 2
is usually sufficient to provide enough filtering for most cases, (2 represents
approximately a 1 second time constant). When the 0.1 degree resolution is
selected this should be increased to 4. If this value is set too high, controllability will
suffer.
S E C O N D
S E C O N D
S E C O N D
S E C O N D
S E C O N DA R
A R
A R
A R
A RY MENU (cont'd)
Y MENU (cont'd)
Y MENU (cont'd)
Y MENU (cont'd)
Y MENU (cont'd)
LPbr
LPbr
LPbr
LPbr
LPbr
Loop Break Protection: Select O F F
O F F
O F F
O F F
O F F,
,
,
,
, 1
1
1
1
1 to 9999
9999
9999
9999
9999 seconds.
I
f, during operation, the
output is minimum (0%) or maximum (100%), and the input moves less than 5°F
(3°C) or 5 counts over the time set for LPbr, the LOOP bAd
LOOP bAd
LOOP bAd
LOOP bAd
LOOP bAd message will appear.
This condition can also be routed to an Alarm Condition if alarms are present and
turned On (see ALbr in the secure menu). The loop break error can be reset by
pressing the ENTER
ENTER
ENTER
ENTER
ENTER key when at the LPbr menu item.
The INDEX
INDEX
INDEX
INDEX
INDEX & E N T E R
E N T E R
E N T E R
E N T E R
E N T E R
keys
m ay also be used.
POL
Process Output Low (936): Select -450°F, -260°C, or -1999 counts to 50 degrees or counts
less than
POH
.
POH
Process Output High (936): Select from 50 degrees or counts greater than
POL
to
+9990°F, +5530°C, or 9990 counts. A voltage output is scalable from 0 to 10 VDC that
represents the Process Variable. To properly scale the output, the values for
POL
and
POH
must be calculated. The simplest example is an output of 0 to 10 VDC from 0 to 200°.
In this example
POL
=0 and
POH
=200. To Calculate POL and POH for other ranges use
the following:
K
= (Highest desired temperature - Lowest desired temperature) /
(Maximum desired voltage - Minimum desired voltage)
POH
= ((10 - Maximum desired voltage) * K) + Highest desired temperature
POL
= ((Minimum desired voltage - 0) * K) - Lowest desired temperature
LOrE
Local / Remote Status (992): Select LOC or rE. When LOC is selected, the host computer
is advised not to send remote commands. When rE is selected, CFLt=2, and nAt is set
> 0, if the control is not accessed by the host computer in the time set in nAt, the control
will revert to the CFSP.
CFSP
Communications Fail Set Point (992): Set to desired value.
Addr
Control Address (992): Set from 1 to FF. This number (hexadecimal, base 16) must match
the address number used by the host computer. Viewed only in this menu.
Содержание CN76000
Страница 1: ...1 MADE IN USA ENTER AL AL INDEX C F SP2 AL SP1 PV SV 949 1241 ...
Страница 28: ......
Страница 29: ......
Страница 30: ......
Страница 31: ......
Страница 32: ......
Страница 33: ......
Страница 34: ......
Страница 35: ......
Страница 36: ......
Страница 37: ......
Страница 38: ......
Страница 39: ......
Страница 40: ......
Страница 41: ......
Страница 42: ......
Страница 43: ......
Страница 44: ......
Страница 45: ......
Страница 46: ......
Страница 47: ......
Страница 48: ......
Страница 49: ......
Страница 50: ......
Страница 51: ......
Страница 52: ......
Страница 53: ......
Страница 54: ......