SECTION 13B. CYCLE TIME (“TIME”)
If you have select
“S.3=P”
in Setpoint 1 Configuration (
“S1.CF”
refer to Section 11), you may
specify a cycle time for the time proportional outputs.
1.
Press the
MENU
button until
“TIME”
appears.
2.
Press the
/
DEV
button. The last previously stored value appears as follows:
If you have selected
“S.5=S”
in
“S1.CF”
, the third digit will flash and you may enter
maximum/minimum values from 0005. through 0199. seconds (unit of measure is second
in this mode).
If you have selected
“S.5=S
”
the Transistor and Relay 1 outputs are both enabled.
or
If you have selected
“
S.5=F”
in
“
S1.CF”
, the second digit will flash and you may enter
maximum/minimum values from 000.1 through 004.9 seconds (unit of measure is 0.1
second in this mode).
If you have selected
“S.5=F
”
only the Transistor output is enabled.
3.
Press the
/
MAX
button to change the value of the flashing digit. If you continue to press
the
/
MAX
button, the flashing digit's value continues to change.
4.
Press the
/
DEV
button to scroll to the next digit.
5.
Press the
MENU
button to store your selection. The meter momentarily shows
“
STRD”
,
followed by
“
S2.DB”
(Setpoint 2 Deadband)
SECTION 14. SETPOINT 2 DEADBAND (S2.DB)
Refer to Table 23-1 for a summary list of menu configuration.
Setpoint 2 Deadband (
S2.DB
) is not active unless your meter has dual relay output capabilities.
The LED's will display whether the (
S2.DB
) is active or not. To set the deadband (hysteresis) of
Setpoint 2, follow these steps:
1.
Press the
MENU
button until the meter shows
“S2.DB”
.
2.
Press the
/
DEV
button. The meter shows the last previously stored 4-digit number
(0000 through 9999) with flashing 4th digit.
3.
Press the
/
MAX
button to change the value of the flashing digit.
If you continue to press the
/
MAX
button, the flashing digit's value continues to change.
4.
Press the
/
DEV
button to scroll to the next digit.
5.
Press the
MENU
button to store your selection.
“STRD”
momentarily displays, followed
by cold junction offset if you have a standard meter (refer to Section 19) or
“OT.CF”
(Output Configuration) if you have analog output capabilities (refer to Section 15).