SECTION 10. READING CONFIGURATION ("RD.CF")
To determine if your meter shows in °F (Fahrenheit) or °C (Celsius).
1.
Press the
MENU
button until the meter shows
“RD.CF”
.
2.
Press the
/
DEV
button. The meter shows one of the following:
*
“R.1=F” (°F)
*
“R.1=C” (°C)
3.
Press the
/
MAX
button to toggle between choices.
4.
Press the
MENU
button to store your selection. The meter momentarily shows
“STRD”
,
followed by
“S1.CF”
(Setpoint 1 Configuration).
SECTION 11. SETPOINT 1 CONFIGURATION (S1.CF)
Setpoint 1 is not active unless your meter has dual relay output capabilities. The LED's will display
whether the (S1.CF) is active or not. You may use Setpoint 1 Configuration (S1.CF) for the following:
*
To set the setpoint's active band above or below your chosen value
*
To select whether the setpoint operation is latched or unlatched
*
To select On/Off or Time Proportional Control
1.
Press the
MENU
button until the meter shows
“S1.CF”
.
2.
Press the
/
DEV
button. The meter shows one of the following:
*
“S.1=A”
(Active above the setpoint) (Factory default)
*
“S.1=B”
(Active below the setpoint)
3.
Press the
/
MAX
button to toggle between choices.
4.
Press the
/
DEV
button again. The meter shows one of the following:
*
“S.2=L”
Setpoint 1 to be latched
*
“S.2=U”
Setpoint 1 to be unlatched (Factory default)
5.
Press the
/
MAX
button to toggle between choices.
6.
Press the
/
DEV
button. One of the following appears:
*
“S.3=O”
Setpoint 1 On/Off control (Factory default)
*
“S.3=P”
Setpoint 1 on Time Proportional Control
7.
Press the
/
MAX
button to toggle between available selections.
8.
If you select
“S.3=0”
(factory default), press the
MENU
button to store.
“STRD”
momentarily appears, followed by
“S2.CF”
(Setpoint 2 Configuration). If you select
“S.3=0”
and press the
/
DEV
button, the meter returns to
S.1
option.
If you select
“S.3=P”
, press the
/
DEV
button. One of the following appears:
*
“S.4=R”
(reverse acting, i.e., for heating)
*
“S.4=D”
(direct acting, i.e., for refrigeration)
9.
Press the
/
MAX
button to toggle between available selections.
10. Press the
/
DEV
button. One of the following appears:
*
“S.5=S”
(slow proportional control, cycle time from 5 to 199 sec)
*
“S.5=F”
(fast proportional control, cycle time from 0.1 to 4.9 sec)
11. Press the
/
MAX
button to toggle between available selections.
Transistor logic out is always enabled for either On/Off or Time Proportional control
modes. Relay #1 is enable for On/Off control and for slow Time Proportional control
(“S.5=S”) modes. Relay #1 is disabled if “S.5=F” (fast mode).
18