Siemens V20_EN_rev01-08032019.docx 

 

11-13 

 

  Motor power (P0307) exceeds invert-

er power capability (r0206). 

  Motor  power  (P0307)  must  match  invert-

er power (r0206) 

Note

: F5 cannot be cleared until the inverter 

overload utilization (r0036) is lower than the 
inverter I

2

t warning (P0294). 

F6 

Chip  temperature 
rise  exceeds  criti-
cal levels 

  Load at start-up is too high 

  Load step is too high 

  Ramp-up rate is too fast 

Check the following: 

  Load or load step too high? 

  Increase ramp-up time (P1120). 

  Motor  power  (P0307)  must  match  invert-

er power (r0206). 

  Use setting P0290 = 0 or 2 for preventing 

F6. 

F41 

Motor  data  identi-
fication failure 

Motor data identification failed. 

  r0949 = 0: No load applied 

  r0949 = 1: Current limit level reached 

during identification. 

  r0949 = 2: Identified stator resistance 

less than 0.1% or greater than 100%. 

  r0949 = 30: Current controller at volt-

age limit 

  r0949  =  40:  Inconsistency  of  identi-

fied  dataset,  at  least  one  identifica-
tion failed 

Percentage  values  based  on  the  imped-
ance Zb = Vmot,nom / sqrt(3) / Imot,nom 

Check the following: 

  r0949 = 0:  is the motor connected to the 

inverter? 

  r0949  =  1  -  49:  are  the  motor  data  in 

P0304 - P0311 correct? 

  Check  what  type  of  motor  wiring  is  re-

quired (star, delta). 

F80 

AI lost input sig-
nal 

  Broken wire 

  Signal out of limits 

 

11.2 

ALERT CODES 

If an alarm is activated the alarm icon shows immediately and then the display shows the alarm code 
proceeded by "A". Note that alarms cannot be acknowledged. They are cleared automatically once the 
warning has been rectified. 

Alarm code list 

Code 

Cause 

Remedy 

A501 

Current limit 

  Motor  power  does  not  corre-

spond to the inverter power 

  Motor leads are too long 

  Earth faults 

See F1 

Small motors (120 W) under FCC 
and  light  load  may  cause  a  high 
current 

Use V/f operation for very small motors 

A502 

Overvoltage limit 

Overvoltage  limit  is  reached.  This 
warning  can  occur  during  ramp 
down,  if  the  Vdc  controller  is  disa-
bled (P1240 = 0). 

If this warning is displayed permanently, 
check inverter input voltage. 

A503 

Undervoltage limit 

  Main supply failed. 

  Main  supply  and  consequently 

DC  link  voltage  (r0026)  below 
specified limit. 

Check main supply voltage. 

A504 

Warning  level  of  inverter  heat  sink 
temperature,  warning  level  of  chip 

Note

r0037 = 0: Heat sink temperature 

Содержание SIEMENS SINAMICS V20

Страница 1: ...Siemens V20_EN_rev01 08032019 docx 0 0 0 INVERTER SIEMENS V20...

Страница 2: ...6 1 6 4 TECHNICAL DATA 6 1 7 POWER WIRING 7 3 7 1 POWER CIRCUIT CONNECTION 7 3 7 2 SAFETY INSTRUCTIONS 7 3 7 3 RULES FOR EMC COMPLIANT MOTOR INVERTER WIRING 7 3 7 4 SIEMENS V20 ELECTRICAL WIRING 7 5...

Страница 3: ...10 9 10 3 PARAMETER LIST 10 9 10 4 CONFIGURATION PARAMETERS 10 9 10 4 1 Upwards 10 9 10 4 2 Power limitation 10 10 10 4 3 Downward 10 11 10 5 RUPTURE VALVE TEST 10 11 11 ACTIVE FAULTS ALERT 11 11 11...

Страница 4: ...starting current peaks The maximum starting current is the rated current In Power factor correction Cos 0 98 Power saving Comfort optimization Setting parameters of high low speed Maximum power absor...

Страница 5: ...on the equipment disconnect the power supply and wait a few minutes for the internal capacitors to discharge 4 The inverter must always be connected to the mains In case of an interruption wait at lea...

Страница 6: ...otors The inverters are available in many frame sizes Component Rated output power Rated in put current Rated out put num ber Order number Filtered Frame size C with single fan 2 2 kW 27 2 A 11 A 6SL3...

Страница 7: ...Siemens V20_EN_rev01 08032019 docx 3 2 3 1 3 Terminal description Terminal layout...

Страница 8: ...Siemens V20_EN_rev01 08032019 docx 3 3 3 1 4 Dimension drawings Frame size C...

Страница 9: ...shielded Shielded EMC compliant RE CE C2 1 Unshielded Shielded EMC compliant RE CE C2 2 Da FSB a FSC 50 m 25 m 25 m 200 m 200 m 5 m 1 For filtered variants only RE CE C2 refers to EMC compliance to EN...

Страница 10: ...t In Peak current Imax Overload MAX A A 3AC 13 6 20 4 150 In x 60s 24 5 In x 240s Rated pulse frequency kHz 4 Power loss kW 0 114 24 VDC supply A 50 mA Fuses Rated current 3NA 3820 50A Connectors Line...

Страница 11: ...the below shown additional requisites are respected Connection by use of a shielded cable at reduced capacity Motor cable shorter than 25 m Pulse frequency 4 kHz Current nominal input current in the...

Страница 12: ...d the devices within the control cabinet have to be assigned to these zones following the rules below The different zones must be electromagnetically decoupled by using separate metallic housings or g...

Страница 13: ...rter handle only the upward travel in consequence of that there are not cur rents generated and MUST NOT BE INSTALLED ANY BRAKING RESISTOR The downward direction is regulated by hydraulic valve To adj...

Страница 14: ...ctions can be made 6 4 TECHNICAL DATA Following there are the technical data related to the user interface terminals No Terminal marking Description 1 10V 10V output tolerance 5 referred to 0V maximum...

Страница 15: ...lity No Response time 4 ms 4 ms Pulse train input No 13 24V 24 V output tolerance 15 to 20 referred to 0 V maximum 50 mA non isolated 14 0V Overall reference potential for digital inputs Digital outpu...

Страница 16: ...tem 2 The power cables for the inverter contactors and contactors motor connection must be as short as possible shielded four core three phases plus yellow green earth wire or four unshielded cables b...

Страница 17: ...to the power cable even if shielded if parallel routing cannot be avoided they must be in sepa rate metal raceways 8 All earth connections must be as short and wide as possible 9 To avoid unwanted tri...

Страница 18: ...ermissible I O terminal cable cross sections Cable type Permissible cable cross section Solid or stranded cable 0 5 to 1 5 mm2 Ferrule with insulating sleeve 0 5 mm2 1 Use shielded screw for analog in...

Страница 19: ...parameters between the inverter and a standard MMC SD card Powering the inverter from the Parameter Loader when mains power is not available 9 2 THE BUILT IN BASIC OPERATOR PANEL BOP The Basic Operato...

Страница 20: ...xt digit Clears faults Long press 2 s Quick parameter number or value edit M OK Hand Jog Auto Press to switch between different modes Note Jog mode is only available if the motor is stopped and it is...

Страница 21: ...ection mode Motor rotates in the reversed direction Inverter is in HAND mode flashing Inverter is in JOG mode 9 2 1 Inverter menu Menu Description 50 60 Hz selection menu This menu is visible only on...

Страница 22: ...es or val ues To increase or decrease the parameter number index or value press or for less than two seconds To quickly increase or decrease the parameter number index or value press or for longer tha...

Страница 23: ...he existing leftmost digit above 9 to add more digits to the left Pressing or for over two seconds enters fast digit scrolling Example 1 Editing parameter numbers Example 2 Editing parameter indices I...

Страница 24: ...g mode the LED flashes green at 0 5 Hz 9 3 QUICK COMMISSIONING 9 3 1 Quick commissioning through the Setup menu Structure of the setup menu The setup menu guides you through the steps required for qui...

Страница 25: ...ond with the wiring of the motor star delta MOT V P0305 0 1 Rated motor current A Note that the input of rating plate data must correspond with the wiring of the motor star delta MOT A P0307 0 1 Rated...

Страница 26: ...o accept the parameter settings from both the currently and the previously selected macros which may lead to undefined and unexplainable operation Funzionalit This menu defines certain common applicat...

Страница 27: ...le edit High speed Low speed Speed of releveling Acceleration deceleration ramps Power limitation ATTENTION Only in case of change of the inverter or of the electric motor you must do motor recognitio...

Страница 28: ...eters PARAMETER CABIN DEPARTURE WITH TEARING CABIN STARTING LATE CABIN SPEEDS UP TOO FAST P1120 increase the value of the parameter decrease the value of the parameter parameter has no effect Setting...

Страница 29: ...BOP see below In general facing to a non compliance detected the inverter behaves as follows Errors Type A Alarm are minor errors that in principle have no influence on the behavior of the inverter LI...

Страница 30: ...in regenerative mode r0949 0 Hardware reported r0949 1 or 2 Software reported Check the following Supply voltage P0210 must lie within limits indicated on rating plate Ramp down time P1121 must match...

Страница 31: ...eck the following r0949 0 is the motor connected to the inverter r0949 1 49 are the motor data in P0304 P0311 correct Check what type of motor wiring is re quired star delta F80 AI lost input sig nal...

Страница 32: ...y reduction de pending on parameterization in P0290 r0037 1 Chip junction temperature includes heat sink Check the following Ambient temperature must lie within specified limits Load conditions and lo...

Страница 33: ...ntrol circuit board if possible by blowing with compressed air or using a vacuum cleaner 2 Make sure no screws are loose in the power or control terminal blocks 3 Make sure inverter operation is norma...