5.5 Set Alarm 1 Relay
1 O2
0 % VOL
SET ALARM 1 RELAY1
1 O2
0 % VOL
3
Allows the user to set which relay is
activated in the event of an alarm1 being
breached on this channel. The main board
has three built in alarm relays. To set one
of these the Relay is set to 1,2 or 3. 1 being
the top relay on the right of the display.
If the user has additional relay boards
installed then the user can select one of
these relays as alarm output. One
additional relay board gives Relays 4 to 11
a second relay board gives relays 12 to 19.
Change the relay to be activated in
the event of an alarm by rotating
the jog wheel. Press the jog wheel
Note that any number of channels can be assigned to the same relay output thus providing for
common alarm output.
The user can set many different relay schemes for each channel.
Alarm if out of band (windowed). O2 depletion / enrichment.
Nominal O2 value 20.9
Setting Alarm 1 as falling with a value of 18 and Alarm 2 as rising with a value of 22. Setting
Alarm 1 relay to the same as Alarm 2 relay the user can wire one input to show out of band.