OLIVER
IGD
OLIVER
IGD
Tocsin 700 Menu System
1. Start up
Time in 24 hour format.
Company name is programmable in
EPROM Memory.
12:23:01
OLIVER IGD LTD
12:23:01
1 FLAM
0 % LEL
WARMING UP
BOILER ROOM 1
2. Warming Up
3. Normal Display Mode
Normal display mode.
In normal display mode the display will
auto scroll through all installed channels
at a user settable time. The time is
settable from 1 to 255 seconds.
Time is user programmable in seconds
and is programmed in the engineering
mode.
Normal display shows current channel in top left corner. Current channels measurement gas, reading
and measurement units.
The gas types are stored in EEPROM and can be reconfigured with the aid of a computer to display
any gas with up to four characters. There are 14 pre-configured gas types. The unit can store up to
sixteen different gas types.
FLAM
CO
NO
NO2
CL2
HCL
HCN
NH3
O2
H2S
SO2
H2
FIRE
CO2
There are three pre-configured measurement types.
%LEL
PPM
%VOL.
The unit can store up to four measurement types. Again these can be reconfigured with the computer
link software.
Warmup is displayed for thirty
seconds.