103
Appendix G |
LEL Correlation
Factors
The following chart outlines LEL correlation factors for combustible
catalytic gas sensors installed in iTrans2.
Methane
Pentane
Hydrogen
Acetone
1.80
0.90
Acetylene
1.40
0.70
Ammonia
1.00
0.50
Benzene
2.10
1.05
n-Butane
1.80
0.90
Ethane
1.40
0.70
Ethanol
1.60
0.80
Ethylene
1.40
0.70
n-Hexane
2.85
1.40
Hydrogen
1.00
Isopropanol
1.80
0.90
JP-4
3.00
1.50
JP-5
3.10
1.55
JP-8
3.20
1.60
Methane
1.00
Methanol
1.35
0.65
n-Pentane
2.00
1.00
Propane
1.60
0.80
Styrene
2.40
1.20
Toluene
2.50
1.25
Xylene
2.40
1.20
Example: The instrument has been calibrated on methane and is now
reading 10% LEL in a pentane atmosphere. To find actual %LEL pentane,
please multiply by the number found at the intersection of the methane
column (calibration gas) and the pentane row (gas being sampled)…in this
case, 2.00. Therefore, the actual %LEL pentane is 20% (10x2.00).
Calibration gases available from Industrial Scientific - Oldham.
Содержание iTrans 2
Страница 6: ...6...
Страница 9: ...9...
Страница 10: ...10...
Страница 19: ...19 Figure 2 5 Electronics Board for Remote Sensor...
Страница 20: ...20...
Страница 22: ...22 Figure 3 1 Mounting the Gas Monitor on a Wall Figure 3 2 Mounting the Gas Monitor on a Column Using U Bolts...
Страница 28: ...28 Figure 4 4 Wiring Diagram for a Single On board Sensor...
Страница 31: ...31 Figure 4 7 Wiring Remote Sensors Back to...
Страница 52: ...52...
Страница 60: ...60...
Страница 66: ...66...
Страница 72: ...72 Figure A 4 Wiring Diagram of Single Sensor HART Supported...
Страница 73: ...73 Figure A 5 Wiring Diagram of Dual Sensor HART Supported...
Страница 80: ...80 Figure A 15 EDD GUI View Figure A 16 PC to HART Interface Wiring Diagram...
Страница 86: ...86...
Страница 90: ...90...
Страница 98: ...98...
Страница 100: ...100...
Страница 104: ...104...
Страница 105: ...105...