© 2015 OJ Electronics A/S
13
room sensors - bus connection
Only OJ units which are suitable for two-wire communication can be used.
Standard installation cable of minimum 2 x 0.25 mm² can be used. Units can be connected in conventional
star formation or in bus mode (daisy chain).
The master has 4 sets of terminals marked SENSOR/CONTROLLER BUS that can be used for connecting
the 2-wire signal cable from the unit.
There are 4 identical sets of terminals for convenient installation. Any unit can be connected to any pair
of terminals. The total length of the 2-wire system can be up to 300 m with a maximum length of 100 m
between any two units. For further information, see the table below.
Remember to c to + and – to – .
table: length of cable
Standard cable
Max. cable length from master to room
controller/sensor with display
Max. cable length from master to room
controller/sensor without display
≥0.25 mm
2
Up to 100 m *
Up to 300 m
≥0.50 mm
2
Up to 200 m *
Up to 300 m
≥0.75 mm
2
Up to 300 m *
Up to 300 m
*) Up to 300 m if operation without backlight is acceptable.
installation
Fig. 9a
BR965A18a
SENSORS/CONTROLLERS CONNECTED IN STAR
Fig. 9b
SENSORS/CONTROLLERS CONNECTED IN BUS MODE
(DAISY CHAIN)
Fig. 9c
SENSORS/CONTROLLERS CONNECTED IN STAR
SENSOR/CONTROLLERS CONNECTED IN BUS MODE
(DAISY CHAIN)