Commissioning mode
Digital masters feature a special “commissioning mode”, which allows supply water temperature to be
controlled to assist the drying out of a newly laid concrete floor.
To start this function:
• Set DIP-4 to “ON”.
• This will maintain the supply water temperature at 23°C for three days and will fully open all manifold
actuators.
• Then, for a further four days, the water will be maintained at the maximum supply water temperature set
in the WLM3 master menu while the manifold actuators will remain fully open.
• When the WLM3 master is operating in commissioning mode, the output LEDs will flash consecutively
and the word “commissioning” will flash on the display.
• The commissioning function is paused if the power supply is interrupted.
• To restart commissioning from the beginning, switch DIP-4 to “OFF” and then back to “ON”.
• To deactivate the function, switch DIP-4 to “OFF”.
• After 7 days, commissioning mode is ended and normal operation is resumed (even with DIP-4 still
“ON”).
NOTE: This function conforms to BS/EN-1264 Part 4.
NOTE: Commissioning mode can only be activated on a WLM3-xFS master, and only if a supply water
sensor is mounted. Otherwise, the function will be interrupted immediately.