background image

 

© 2015 OJ Electronics A/S

14

setting the channel

Each room sensor can be set to operate a specific output which in turn controls a thermal actuator 

on the manifold. A selector can be accessed under the front cover of the unit where the number of its 

output (i.e. its channel number) can be set with a screwdriver (see fig. 10). Up to 14 channels can be 

set on the selector, and there are two auxiliary channels (see later). A WLM3 master has 8 outputs. It 

can be connected with an add-on slave module with an additional 6 outputs, creating a system with 14 

individual zones.

Please note that channels 10 to 14 are marked as A through E on the selector, 

A room sensor set for channel 1 will activate the thermal actuator connected to output 1 on the master.

The channel number can be set before power is connected to the system. The channel set on the room 

sensor can be changed afterwards if needed.

If two room sensors are placed in the same room and set to the same channel, temperature will be 

controlled by the average of the temperature recorded by both units.

Channel 0:

Each Room sensor is delivered with the switch in position 0. It must therefore be set to operate correct 

channel output. Channel 0 can also be used for a room controller which is only used to control a group 

(area) of room sensors without actually controlling the room in which it is installed (e.g. a controller in 

the kitchen which is only used to control sensors located in other rooms). Setting the room controller 

to channel 0 means that times and temperatures must be set on the WLCT3 for the group (area). The 

WLCT3 will not, however, control a specific output itself.

Channels 1..14:

A room sensor set for Ch1 will activate the thermal actuator connected to output 1 on the master. If 

several room sensors are set to the same channel number, heating will be controlled in the following 

way:

- Actual room temperature will be calculated as an average. 

- The room temperature setpoint will be calculated as an average.

- If floor sensors are connected to the room sensors:

The lowest value of any floor sensor is used as the minimum limit temperature.

The highest value of any floor sensor is used as the maximum limit temperature.

Channel 15 

 (position F on the switch): Party and holiday function.

Special function. “Special Features” for further instructions.

testing the system:

 See “Guidelines and Special Features – Power-up recommendations”. 

installation

Fig. 10

BR1026A07

a

© 2015 OJ Electronic  

A/

S

Jumper

-G

B

    

BR1026A07a

Содержание WLCT3

Страница 1: ...2015 OJ Electronics A S 67345 02 15 HKT WLDT3 www ojelectronics com Installation Manual WLM3 WLCT3 WLTD3 WLTA3...

Страница 2: ...ures the best possible comfort conditions and also reduces energy consumption Highlights of the system depending on the units connected Heating and cooling control for true comfort Humidity sensor to...

Страница 3: ...0 Certifications 30 Disposal and recycling 30 Technical specifications 31 Waterline Add On Module Type WLM3 xAO 33 Overall system configuration 33 Technical specifications 33 Waterline Outdoor Compens...

Страница 4: ...OFF Common UHF PUMP Commission mode X RELAY Learn mode Boiler test Install mode WLM2 Compatible ON OFF Control String number 1 F Unit number 1 9 BR1025A11a BR1025A10a 2015 OJ Electronic A S 9 10 GB O...

Страница 5: ...OFF Common UHF PUMP Commission mode X RELAY Learn mode Boiler test Install mode WLM2 Compatible ON OFF Control String number 1 F Unit number 1 9 BR1025A11a BR1025A10a 2015 OJ Electronic A S 9 10 GB O...

Страница 6: ...2015 OJ Electronics A S L N L N BR1025A08a 2015 OJ Electronic A S WLOC3 GB Wiring diagram WLM3 AO Continuously PE only BR1025A08a 6 WLM3 underfloor heating controller...

Страница 7: ...mmunication can be used For information on previous generations see Special Features Replacing old masters Description Product programme Product Thermoheads Type Master for 8 zones 230V AC WLM3 1BA ba...

Страница 8: ...g with one or more thermal actuators These zones are referred to later in this manual as channels 1 to 8 If more than eight zones are to be controlled it is necessary to install an add on AO module wh...

Страница 9: ...nuously PE only Electrical installation Boiler demand heat source The master has a volt free relay output that can be used to control a boiler heat pump or to open a motorised valve A To control a hea...

Страница 10: ...delay allows time for the thermal actuator to start opening The 230V AC pump can be connected directly to terminals L and N under the heading SEC UHF PUMP Connect the pump PE earth terminal to the PE...

Страница 11: ...ovide cooling water The relay is ON when there is a cooling demand For further information see Using cooling functions Cooling device module alternative The relay output is always ON in cooling mode a...

Страница 12: ...ete check that the room sensor in for example room zone 1 operates the thermal actuator s on the manifold intended for that room If the actuators appear to be in the wrong position on the manifold it...

Страница 13: ...length of the 2 wire system can be up to 300 m with a maximum length of 100 m between any two units For further information see the table below Remember to connect to and to Table Length of cable Sta...

Страница 14: ...st therefore be set to operate correct channel output Channel 0 can also be used for a room controller which is only used to control a group area of room sensors without actually controlling the room...

Страница 15: ...om controllers sensors Initialize analogue room sensors WLTA3 WLTD3 and WLTM3 by removing the plastic battery pull tab or pressing the internal initialization button learning mode button until a beep...

Страница 16: ...will vary the supply water temperature setting according to the outdoor temperature A standard factory programmed compensation curve is used for this purpose If needed the curve can be changed see sep...

Страница 17: ...ug in connectors RJ14 For connecting WLM3 add on modules to WLM3 masters a plug in connector is provided with the add on module Similarly a WLRC3 wireless receiver is connected to a WLM3 master using...

Страница 18: ...be connected in a daisy chain NOT in a star formation see fig 13c An FS master can be used as the network controlling master to control central mixing of the supply water and boiler activation The ne...

Страница 19: ...al to control a chiller reversible heat pump or diverting valve see Free relay function X OUTPUT With BA masters where dew point control is required it is also necessary to install a sensor ETF 522 on...

Страница 20: ...troller to the corresponding number The special radiator controller is available in wired or wireless version NOTE When the WLCT3 is in radiator mode and heat is demanded it does not start the circula...

Страница 21: ...off pipe immediately above the storage cylinder Use a fixing strap to attach it tightly to the surface The WLCT3 should be installed in a convenient position for the user With the WLCT3 in hot water m...

Страница 22: ...commissioning mode the output LEDs will flash consecutively and the word commissioning will flash on the display The commissioning function is paused if the power supply is interrupted To restart comm...

Страница 23: ...witching DIP 3 to ON 6 If the sensor controller is wireless press the learning mode button on the sensor controller See Installation under Waterline Room Sensors Type WLTx If the sensor controller is...

Страница 24: ...the actuator on output 1 should activate opening after a 1 3 minute delay depending on the type of actuator Important If the room sensor controller is of wireless type a delay of up to 5 minutes may o...

Страница 25: ...r Settings Factory settings BA FS Cooling mode Day cooling temperature Day heating temperature 3 0 C Night cooling temperature Day cooling temperature 3 0 C Dew point safety zone Dew point 3 0 C Room...

Страница 26: ...system The error can be corrected by setting the channel number of the unit to one that exists in the installed master add on module system E3 3 flashes Application sensor defective The fault can only...

Страница 27: ...ng cooling mode but the channel is already active engaged Channels 2 14 used as step 2 output in 2 step mode but the channel is already active engaged Channels 1 14 used for humidification humidity se...

Страница 28: ...ld not be simpler On the right hand side of the controller is a slide switch with four positions which determines system functionality AUTO This allows the system to run automatically according to the...

Страница 29: ...nsor controller is found the system will run constantly at 20 ON If an outdoor sensor is connected the system will run at 40 at outdoor temperatures of 10 C or lower decreasing to 0 at 20 C or more Th...

Страница 30: ...aster CE 1993 68 EEC LVD low voltage directive 2006 95 EC EMC electromagnetic compatibility 2004 108 EC RoHS restriction on the use of certain hazardous substances 2011 65 EU WEEE waste electrical and...

Страница 31: ...valves 8 outputs max 2 A direct Boiler max 5 A voltage free Main pump max 5 A voltage free Sec pump max 5 A direct Control input Setback temperature etc Temperature settings permanent settings Room t...

Страница 32: ...erature settings Factory settings Range Room temperature 21 C 5 40 C Setback temperature 18 C 5 40 C Frost protection 5 C 3 8 C Max floor temperature 27 C 20 40 C Min floor temperature 17 C 10 30 C Ma...

Страница 33: ...xAO which provides another six outputs The AO module then controls channels 9 to 14 9 E on the hex encoder Connection of master and add on module Connect the AO module using the special cable included...

Страница 34: ...t sources e g ventilation vents must be avoided The unit should be mounted vertically with the cable entry downwards Bus connection Only OJ units which are suitable for two wire communication can be u...

Страница 35: ...s can be connected to a master or a master add on system using the RJ sockets provided Additional receivers can be connected if necessary please ask your distributor s technical department The master...

Страница 36: ...ol over Area 1 The WLTA3 sensor installed in Area 1 now has a control range of 18 C 22 4 C to 24 C 22 4 C In addition to the standard WLCT3 room controller you may have added one of the following to y...

Страница 37: ...ontrolled from this WLCT3 must be selected NOTE If you need to adjust the time at a later date insert a pin into the hole marked for setting the clock AREA SETUP see next page Press the UP or DOWN but...

Страница 38: ...utput on the master which controls the valve actuator for that room Example A system may have the kitchen room sensor operating master output 4 and the children s room sensor operating master output 5...

Страница 39: ...ormation on programming see Programming 4 Event Clock Time and Temperature Comfort mode Temporary override To temporarily override any temperature in the 4 event schedule press the UP button once to s...

Страница 40: ...can now be repeated for the second third and fourth events These settings will be valid for days 1 5 as shown on the display To program days 6 and 7 repeat the above Days 6 and 7 are usually Saturday...

Страница 41: ...oom temperature Outdoor temperature If no sensor is installed OFF is displayed Press the UP or DOWN button to view the various read outs No changes can be made here Use the OK button to exit App Appli...

Страница 42: ...tolerance before the second output is allowed to activate The menu is only shown if 2 step mode is set to ON timE sets the time during which temperature is permitted to be too low before the second ou...

Страница 43: ...s Indicated by Code 2 52 Select the required sequence with the OK button Escape without any changes Hi Li Floor sensor Max and min permissible floor surface temperatures A floor limit sensor can be co...

Страница 44: ...hannels set as part of the WLCT3 area will follow the automatic temperature settings of this room controller 4 event timer min and max floor temperature limits Set a channel room to ON if it is to be...

Страница 45: ...channel will always be ON cannot be set to OFF AdAP Adaptive function This function enables the thermostat to calculate when it needs to switch the heating ON to ensure that the required temperature...

Страница 46: ...N Ch 2 Living room ON 4 event times and temperatures Own settings Standard Mode Radiator mode 2 step mode Hot water mode Time Temperature Temperature Temperature Temperature Time Temperature Days 1 5...

Страница 47: ...ly be activated if the required temperature cannot be achieved by the underfloor heating alone within a preset time period The room controller is used as a standard WLCT3 If required the settings for...

Страница 48: ...e available and allows connection of a floor sensor for minimum or maximum floor temperature limitation instructions Introduction Getting started Waterline Room Sensor with Display Type WLDT3 BR1026A1...

Страница 49: ...ng with the actual temperature The temperature is now controlled only by the master s comfort setpoint factory setting 21 C overriding any programmed 4 event schedules in the system Use the UP or DOWN...

Страница 50: ...iew the room and floor temperatures actually measured The floor temperature is only shown if a floor sensor is installed Software version Room temperature Floor temperature If no sensor is installed O...

Страница 51: ...can be used Units can be connected in conventional star formation or in bus mode daisy chain The master has four sets of terminals marked SENSOR CONTROLLER BUS that can be used for connecting the 2 wi...

Страница 52: ...erate correct channel output Channel 0 can also be used for a room controller which is only used to control a group area of room sensors without actually controlling the room in which it is installed...

Страница 53: ...has been selected on their built in slide switches their temperature settings will be as programmed in the WLCT3 room controller and not in the master Local 4 C adjustment will however still be possi...

Страница 54: ...read the true temperature of the floor and should always be within the heated area To ease replacement we recommend that all floor sensors are mounted in a tube positioned between two heating pipes Th...

Страница 55: ...2015 OJ Electronics A S 55...

Страница 56: ...ark warminster wiltshire ba12 8sp united kingdom T 44 01985 213 003 F 44 01985 213 310 sales ojuk co uk www ojUK co uk OJ ELECTRONICS A S c o Robert Bielecki UL walbrzyska 33 58 160 SWIEBODZICE POLska...

Отзывы: