I N S T R U C T I O N S

© 2014 OJ Electronics A/S

 

 1

67048B 07/14 - (OSH)

Type OJ Air2 Master

• English
• Deutsch
• Français
• Svenska
• Norsk
• Dansk

English

LIST OF FIGURES

The following figures are located at the back of the instructions:

Fig. 1:   Dimensions, front view 

Fig. 2:   Dimensions, side view 

Fig. 3:   Configuration, complete with 2 x Fan IO

Fig. 4:   External communication ports

Fig. 5:   Internal communication ports

Fig. 6:   Connections in RJ12 port for internal communication 

Fig. 7:   Electrical terminal connections 

Fig. 8:   Inserting the SD card

Fig. 9:   OJ Air2 Master, rear view 

Fig. 10:  OJ Air2 Master, 45° view of top 

Fig. 11:  Cable for external Modbus connection

INTRODUCTION

OJ Air2 Master is an intelligent, freely configurable controller for the OJ 

Air2 system. OJ Air2 Master contains a wide range of installations, each 

of which can be configured to ensure perfect adaptation to the ventilation 

system concerned and the provision of precisely the functions needed for 

energy-optimised control. 

The system is configured directly in the built-in Web server via a standard 

IE browser on a PC. 

Thanks to the multi-level user interface, the system designer can create 

different access levels for various user groups. 

The ventilation system is operated from a PC via the built-in Web server 

or from the hand terminal via its unique "turn and push" button. OJ Air2 

Master handles all control functions and communication to and from the 

system. 

OJ Air2 Master contains several different interfaces for peripheral units, 

allowing it to be connected to sensors, pumps and valves.

OJ AIR2 Master can be connected to a BMS system via interfaces such as 

Modbus RTU, Modbus TCP/IP, BACnet and LON.

PRODUCT PROGRAMME

Type

Product

OJ Air2 Master

Controller for air handling unit, Modbus, IP20

OJ Air2 Fan IO

IO module with two pressure transmitters and ana-

logue/digital inputs and outputs 

OJ Air2 HTERM

Hand terminal for system operation

OJ Air2 EXT

Expansion module

OJ Air2 LON

LON module for connection to BMS system 

OJ Air2 EC

EC controller for EC motor

OJ FC

Frequency converter for motor mounting

OJ FC-W

Frequency converter for wall mounting

RHX2M

Controller and step motor for rotary heat exchanger 

with Modbus communication

CONFIGURATION

At the factory

The system designer configures the ventilation system at the factory via the 

user-friendly OJ Air2 Master Web interface and saves the settings in a data 

file containing application and system parameters. 

At the installation site

Once the system has been installed, it is tested and commissioned by a 

technician, who sets energy-optimising and other user specific parameters 

on site. 

Daily operation

Everyday users operate the system via the built-in Web server or the hand 

terminal. 

Configuration of ventilation application

OJ Air2 Master can be configured for a wide range of individual ventilation 

applications, which can be freely combined as desired or required by the 

ventilation system. 

FUNCTIONS

Available ventilation functions

Temperature control:

•  Constant inlet temperature

•  Constant extract temperature

•  Constant room temperature

•  Constant temperature differential 

•  Outdoor temperature compensated inlet temperature

•  Summer/winter compensation

•  Recirculation, night-time heating

•  Summer night cooling

•  Forced cooling

Fan control: 

•  Constant flow

•  Constant pressure

•  Inlet pressure as slave

•  Extract pressure as slave

•  Constant CO2

•  Low speed/high speed (recirculation)

•  Constant operation

•  Automatic operation

Fire:

•  Fire in air handling unit

•  Fire in duct system

•  Fire alarm from ABA 

Other functions

•  Electric heating battery

•  Hydronic heating battery

•  Cross-flow heat exchanger

•  Rotary heat exchanger

•  Fluid-coupled exchanger battery

•  Hydronic cooling

•  DX cooling 

•  Control of damper motors

•  Fault log

•  Alarm management

•  Modulated recirculation 

•  Automatic summer/winter time

UPDATING SOFTWARE

OJ Air2 is equipped with a standard SD card reader and a standard SD 

card is used to update OJ Air2 Master software. To update the OJ Air2 

Master software version, the SD card must contain two files: a win.zip file 

and a .crc file, both of which must be located in the "root directory" of the 

SD card. 

Insert the SD card with the two files into the card reader. The OJ Air2 

Master will then check the content of the card and, if the SD card contains 

a higher software version than that which is already installed on the OJ Air2 

Master, updating will be started when the "turn and push" button of the OJ 

Air2 hand terminal is pressed. The SD card must not exceed 8 GB.

NOTE! The SD card must be inserted into the OJ Air2 Master with the  

connectors facing forwards (fig. 8).

Содержание Air2 Master

Страница 1: ...communication CONFIGURATION At the factory The system designer configures the ventilation system at the factory via the user friendly OJ Air2 Master Web interface and saves the settings in a data file...

Страница 2: ...1 should be connected to the Din 1 input terminals 3 4 Digital input 2 should be connected to the Din 2 input terminals 4 5 Note terminal 4 is shared by Din 1 and Din 2 Digital input 3 should be conn...

Страница 3: ...supply for OJ Air2 Master No communication between PC and OJ Air2 Master which are connected via router The IP address is allocated from the router Wrong IP address Read off the OJ Air2 Master IP addr...

Страница 4: ...e K hlung L fterregelung Konstanter Luftstrom Konstanter Druck Zuluftdruck m Slave Abluftdruck m Slave Konstantes CO2 Niedrige Drehzahl hohe Drehzahl Umluft Konstanter Betrieb Automatikbetrieb Brand B...

Страница 5: ...gitalen Ausg nge 3 7 d rfen max an 30 V angeschlossen werden Digitalausgang 3 ist an Ausgang Dou 3 an den Klemmen 28 und 29 anzuschlie en Digitalausgang 4 ist an Ausgang Dou 4 an den Klemmen 30 und 31...

Страница 6: ...ollieren Falsche Konfiguration der digitalen Eing nge Konfiguration im Men OJ Module Konfigurieren kontrollieren und ggf mittels Ihrem Web Browser korrigieren Die Spannungsversorgung zum OJ Air2 Maste...

Страница 7: ...lation chauffage de nuit Refroidissement de nuit d t Refroidissement forc Contr le de ventilateur D bit constant Pression constante Pression d entr e en esclave Pression de sortie en esclave CO2 const...

Страница 8: ...ants Sorties num riques L OJ Air2 Master est muni de sept relais num riques de sortie avec contacts secs Les sorties num riques 1 2 peuvent tre raccord es max 230 V CA CC AC1 La sortie num rique 1 doi...

Страница 9: ...se adresse IP Notez l adresse IP de l OJ Air2 Master l aide de l OJ Air2 HTERM et entrez la dans le champ d adresse de votre navigateur Mauvaise adresse IP dans le navigateur Entrez la bonne adresse I...

Страница 10: ...rkompensering tercirkulation nattuppv rmning Sommarnattskylning Kylforcering Fl ktstyrning Konstant fl de Konstant tryck Inbl sningstryck med slav Utsugningstryck med slav Konstant CO2 L g hastighet h...

Страница 11: ...utg ng 7 ska anslutas till utg ngen Dou 7 p plintarna 36 och 37 Elanslutningen visas i fig 7 Analoga utg ngar OJ Air2 Master har tre analoga utg ngar 0 10 V DC f r eventuell anslut ning av styrsignal...

Страница 12: ...ktig konfigurering av de digitala ing ngarna Kontrollera och korrigera vid behov i menyn OJ Moduler Konfigurera med hj lp av din webbl ddrare Str mf rs rjningen till OJ Air Master r avst ngd Sl p str...

Страница 13: ...emperatur Utekompensert tilluft Sommer vinterkompensering Resirkulering nattoppvarming Sommernattskj ling Kj leforsering Vifteregulering Konstant flow Konstant trykk Tilluftstrykk m slave Avluftstrykk...

Страница 14: ...p fig 7 Analoge utganger OJ Air2 Master er utstyrt med 3 stk 0 10 V DC analoge utganger til bruk for ev tilkobling av styresignal for varmebatteri roterende varmeveksler eller spjeldmotor p kryssvarm...

Страница 15: ...er elektrisk tilkobling og klemmekoblinger Feil konfigurering av digitale innganger Kontroller og rett ev konfigurasjonen under menyen OJ moduler Konfigurer ved hjelp av din nettleser Str mmen til OJ...

Страница 16: ...erkompensering Recirkulering natopvarmning Sommernatsk ling K leforcering Ventilatorregulering Konstant flow Konstant tryk Indbl sningstryk m slave Udsugningstryk m slave Konstant CO2 Lav hastighed h...

Страница 17: ...onteres p Dou 7 udgangen p klemmerne 36 37 Elektrisk tilslutning fremg r af fig 7 Analoge udgange OJ Air2 Master er forsynet med 3 stk 0 10 V DC analoge udgange til brug for evt tilslutning af styresi...

Страница 18: ...er Forkert konfigurering af digitale indgange Kontroll r og ret evt konfigurationen under menuen OJ Moduler Konfigurer ved hj lp af din Web browser Der er slukket for sp ndingsforsyningen til OJ Air2...

Страница 19: ...85 B RS485 C Aou1 Aou2 Aou3 Dou1 Dou2 Dou3 Dou4 Dou5 Dou6 Dou7 A B 1 2 FIRE Din1 Din2 Din3 Din4 Din5 Din6 VAV CO2 Ain1 VAV CO2 Ain2 24V Aou Ain2 Tin1 PT1000 Sensor Ain1 Tin2 PT1000 Sensor Aou1 Actuato...

Страница 20: ...h 2 x Fan IO Fig 4 External communications ports Fig 2 Dimensions side view Fig 5 Internal communication ports Fig 6 Connections in RJ12 port for internal communication OJ Electronics A S Stenager 13B...

Отзывы: