The S203 keeps the temperature of domestic hot water at the des-
ignated value. Because of the danger of bacteria, it is recommend-
ed that the domestic hot water temperature is not permanently set
below +55 °C.
The upper part of the accumulator is heated by a compressor and,
if necessary also by an electric heater, so that hot domestic water
is obtained.
Main menu
H1 Control circuit
H2 Control circuit
DHW Control circuit
Alarms
>
>
>
>
DHW Info
Domestic hot water setting values
Supply water temperature
Circulation water temp.
HW tank bottom temperature 48.4
HW tank top temperature 51.3
----- ACTUATOR CONTROL ---------------------
Actuator control 75 %
58.0 °C>
54.6°C>
53.2°C>
4 Domestic hot water control
Info-menu shows the domestic hot water settings, the measure-
ments and actuator control related to the domestic hot water.
DHW Control circuit
Info
Setting values
Control mode Automatic
Trend display
>
>
>
>
Setting values
Info
Setting name
Factory
setting
Range
Explanation
Domestic hot water setting value
58.0 °C
20...90 °C
Domestic hot water temperature setting.
Anticipation control
In use
In use/
Not in use
Anticipation speeds up regulation when water consumption
changes by using measurement information from the circulation
water sensor.
DHW reduction/incr. Time program
Not in
use
Not in
use/ In use
The amount of the temperature reduction of DHW in time pro-
grams.
DHW reduction amount
10.0 °C
0...30 °C
The amount of the temperature reduction of DHW in time pro-
grams.
DHW increment amount
10.0 °C
0...30 °C
The amount of the increment of DHW in time programs.