SUM ALARM

Output

Name

Selection

Information about alarm classes

Y4 (66 ja   67)

Sum alarm 

 1-class  
 2-class 
 3-class  
 1-, 2- or 3class  
 1- or 2-class  
 2 -or 3-class  
 1- or 3-class 

Class 1 is for alarms classified as urgent that should al-
ways be immediately forwarded. These include freezing 
risk alarms, pump alarms or sensor fault in supply water.

Class 2 includes e.g. room and outdoor temperature 
sensor fault alarms.

When a sum alarm is activated, the 10VDC control is 
activated (connector 66).

Renaming

Name of meas.:

Approve: Press OK a number of secons
Cancel: Press ESC a number of secons

e n e

r a

l

c o

n

m

s

p

a

e

Navigate to ”Name of measurement” and press OK. A naming dialogue will open. Turn 
the selection knob and accept a letter by pressing OK.

Continue to the next input field by pressing OK. 
Return to the previous input field by pressing ESC. 
Press OK for extended period of time to accept. 
Press Esc for extended period of time to exit without saving any changes.

G

ACTUATOR CONTROLS

Name

Output

Actuator selection

Running time / factory setting (setting range)

H1 

Actuator control

AO1

AO1

 0-10 V /   2-10 V /

 10-0 V /   10-2 V/

 3-point  (TR1, TR2 )

Running time open ____ 150 s (10...500 s)

Running time close ____ 150 s (10...500 s)

H2 

Actuator control

AO3

AO3

 0-10 V /   2-10 V /

 10-0 V /   10-2 V 

Running time open ____ 150 s (10...500 s)

Running time close ____ 150 s (10...500 s)

DHW 

Actuator control

Geopro SH: 

Distribution 

vave, actuator control

AO5

AO5

TR5, TR6

TR5, TR6

 0-10 V /   2-10 V

 10-0 V /   10-2 V

 3-point (TR5, TR 6)

 3-point (TR5, TR 6)

Running time open ____ 15 s (10...500 s)

Running time close ____ 15 s (10...500 s) 

H1

 Actuator control 2  

(serial driving)

AO2

AO2

 0-10 V /   2-10 V 

 10-0 V /   10-2 V

Running time  ____ 150 s (10...500 s)

H2 

Actuator control 2  

(serial driving)

AO4

AO4

 0-10 V /   2-10 V 

 10-0 V /   10-2 V

Running time  ____ 150 s (10...500 s)

DHW 

Actuator control 2  

(serial driving)

AO6

AO6

 0-10 V /   2-10 V 

 10-0 V /   10-2 V

Running time  ____ 15 s (10...500 s)

PUMP CONTROLS

Name

Output

Control mode

Manual control

Attention!

P2 

Pump control (H1)

TR3

   Automatic 
   Manual -> 

  Stop 
   Run  

An auxiliary relay with a coil volt-
age of 24 Vac should be used in 
pump connection.

P3 

Pump control  (H2)

TR4

   Automatic 
   Manual -> 

  Stop 
   Run  

An auxiliary relay with a coil volt-
age of 24 Vac should be used in 
pump connection.

Содержание S203

Страница 1: ...Controller for three circuits control for 2 heating circuits 1 domestic hot water control USER MANUAL USER MANUAL S203 OILON L MP SS YM0055 Version1 0...

Страница 2: ...sons in maintenance or who has in depth knowledge of the control process The S203 is a heating controller for 3 circuits two heating circuits and one hot water circuit Wiring and configurating selecti...

Страница 3: ...trol 18 4 1 Time programs 20 5 Distribution valve control 22 6 Geothermal heating 22 6 1 Setting values 22 6 2 Status 23 7 Alarms 25 8 System settings 29 8 1 Setting date time and language 29 8 2 Text...

Страница 4: ...information for monitoring operation of the unit Favourite views that can be changed by us ers enable them to easily access desired menus Setting values needed by the user can easily be found in the v...

Страница 5: ...m signal stops and the last alarm windows disappear from the display You may look into the alarms later by going to Alarms Active alarms If an alarm has not been acknowledged an exclamation mark will...

Страница 6: ...Heating curve Setting values Control mode Time programs Automatic Automatic DHW Domestic hot water control Info Setting values Control mode Automatic Alarms Active alarms Alarm history Acknowldge all...

Страница 7: ...rn water 22 0 C H1 Room temperatur 21 5 C H1 Actuator control 22 H2 Supply water 28 1 C H2 Return water 21 1 C If a GSM modem is connected to the controller you can read measure ment information with...

Страница 8: ...ng Outdoor temperature M1 H1 Supply water M2 H2 Supply water M5 Accumulator upper part M10 Accumulator lower part M11 Hot gas temperature M12 Compressor s running information NO M13 P2 Pump Alarm Indi...

Страница 9: ...sist r Heating boiler Changing valve VV Domestic water connections Domestic hot water boiler M2 M10 M11 M12 M7 Act 2 Act 1 M5 H1 H2 Measurement Range Measurement information Geopro SH H1 Supply water...

Страница 10: ...the pre increase operation can in crease the temperature of supply water Force control effect Supply water has been forced permanently to the desired temperature reduction level see Control mode selec...

Страница 11: ...t measured supply water temperature Outdoor temp The measured outdoor temperature Outdoor temperature data is displayed if the delayed outdoortemperatureisnotusedinsupplywatercontrol Delayed outdoor t...

Страница 12: ...at the outdoor temperatures 20 C 10 C and 0 C Setting Factory setting Explanation 5 point curve Heating curve 20 58 C 0 41 C 20 18 C Min limit 18 Max limit 75 10 50 C 10 28 C 20 20 0 C 20 40 60 80 Wi...

Страница 13: ...ax limit 45 20 20 0 C 20 40 60 80 1 Radiator heating normal default Heating curve 20 50 C 0 37 C 20 18 C Min limit 18 Max limit 75 10 44 C 10 28 C 20 20 0 C 20 40 60 80 2 Radiator heating steep curve...

Страница 14: ...on and the valve returns back to control mode Pump summer stop In use In use Not in use If the controller is connected to control the pump the pump can be stopped when the summer function is active V...

Страница 15: ...configuration H1 H2 Actuator control Manual mech control Available If you want the voltage controlled actuators to be controlled by manu al mechanical control H1 actuator power supply must come from...

Страница 16: ...reases supply water temperature at the end of the reduction phase Normal temperature has already been reached when the heating mode changes to normal heat Set switch time Set state desired temp level...

Страница 17: ...program 3 5 3 Special days You can enter special day programs as exceptions to normal week ly schedule You can designate a maximum of 7 special day po grams SD A special day program is typically crea...

Страница 18: ...er control Info menu shows the domestic hot water settings the measure ments and actuator control related to the domestic hot water DHW Control circuit Info Setting values Control mode Automatic Trend...

Страница 19: ...sition 20 Manual mechanical Manual mechanical control option must be taken into use Connections and configuration DHW Actuator control Manual mech control Available If you want the voltage controlled...

Страница 20: ...rately Press OK to accept 3 Press OK and then turn the control knob to set the temperature level Drop ON Increase ON normal Press OK to accept 4 Press OK at each weekday you wish to choose 5 Press OK...

Страница 21: ...edule You can designate a maximum of 7 special day po grams SD A special day program is typically created for each holiday When the special day program will be applied it is set in the exception sched...

Страница 22: ...splay shows the top input setpoint and the measured temperature as well as the desired actuator position The control of the distribution valve is normally automatic but it can also be manual controlle...

Страница 23: ...sed heating time the temperature of the hot domestic water boiler s lower part is raised to the set value at measuring point 11 This function can be activated with a separate switch placed e g in the...

Страница 24: ...eating water leaving the geothermal appliance Extra heating Extra heating time 50 2 40 55 C 0 6h When the Extra heating button is pressed the setting changes from Boiler down MIN limit to the Extra he...

Страница 25: ...out of use Informational measurement 10 s 10 s 1 s 2 2 2 2 5 TMW TMS Sensor fault H2 Supply water Valve remains in the position it was in before the sensor defect 20 s 1 s 1 1 6 TMW TMS Sensor fault...

Страница 26: ...d by the electric ity distribution cabinets or the low pressure pressostate acknowledged by the pressostat Geopro GS Controller is not receiving the running information from the compressor even it sho...

Страница 27: ...The controller sends a message showing the last 10 alarms Message is informational Alarm receivers Alarm history Alarm receivers Reset alarm history ACTIVE ALARMS Every active alarm is shown in a sep...

Страница 28: ...e the exact switch times and names of alarm teams or if you wish to edit remove or add switch times press OK at any weekday Adding a new switch time 1 Press OK at the Add new row 2 Press OK Set the sw...

Страница 29: ...1 Set day and press OK to accept name of weekday is updated au tomatically 2 Set month and press OK to accept 3 Set year and press OK to accept 4 To exit without saving and changes press Esc The langu...

Страница 30: ...troller sends a message where is a list of key words text message communication is ok If the controller doesn t send a text message enter the message center number makepowercutandturnitback Retestthet...

Страница 31: ...date network settings System settings Network settings System settings Time 17 01 Date 10 12 2020 Language English SMS settings Network settings Display settings Type info Lock code Not in use Backup...

Страница 32: ...f you know DHCP service exists in the network if you wish to use a fixed IP address 1 First set DHCP function On After the settings have been set successfully set DHCP Off 2 Change only IP address man...

Страница 33: ...rom any port to the port 123 and the receipt of the reply message to this port Access Oulink and M Link supports Ouman Access service which gives you a secure remote connection to the S203 device With...

Страница 34: ...ode The factory set ting of lock code is 0000 2 Turn the control knob and press OK to accept each number Press ESC to return to the previous square 3 Press OK for a number of seconds to accept the cod...

Страница 35: ...lay is connected to S203 to RJ 45 port II Cable max length 10 m External display 2 3 11 12 20 13 21 14 22 15 23 16 24 17 25 18 26 19 27 28 1 5 6 31 32 40 33 41 34 42 35 43 36 44 37 45 38 46 39 47 48 4...

Страница 36: ...trolled actuator 2 serial driving 24 VAC 24 VAC 53 55 56 63 65 65 54 3x0 8 3x0 8 3x0 8 0 10V DC ctrl 0 10V DC ctrl Open Close AO1 AO2 Y1 output Y2 output TR1 TR2 Actuators control of H1 Heating circui...

Страница 37: ...VAC 2x0 8 A1 NO 10 VDC output C NC A2 66 Y4 67 120 120 BG A1 A2 Master device S203 Slave device Data Data 3 5 6 A BG B The controller uses a 230 VAC operating volt age whereby the power supply is sup...

Страница 38: ...uration Check the functions which have been taken in use in the controller X If the measurement shows 0 5 C too much set the offset to 0 5 C You can choose between the measurement channels M1 to M13 a...

Страница 39: ...controller sets pump on but it s not started The alarm has a 5 s delay Pump alarm Nameable alarm M16 Alarm 16 Indication P3 Indication Name P3 Pump P3 Alarm Alarmpriority___ 1 Emergency Digital input...

Страница 40: ...Running time factory setting setting range H1 Actuator control AO1 AO1 0 10 V 2 10 V 10 0 V 10 2 V 3 point TR1 TR2 Running time open ____ 150 s 10 500 s Running time close ____ 150 s 10 500 s H2 Actu...

Страница 41: ...he factory default setting for the damping point is 7 C At a value setting of more than 17 C parallel shift damping is not enabled the function is not available if room temperature mea surement is con...

Страница 42: ...controller indicated H1 supply water temperature 5 C and the temperature of the controller s lower part meas 11 rises above the Accumulator Lower part MIN Accumulator Lower part hysteresis temperature...

Страница 43: ...the compressor every 60 minutes The electrical heating resistor switches off when the temperature of the accumulator s upper part meas 10 rises above the Upper part setting Accumulator Upper part hyst...

Страница 44: ...r Upper part MIN Accumulator Upper part hyster esis and the temp of the accumulator s lower part meas 11 exceeds the controller indicated temp of H1 supply water 5 C and the temp of the accumulator s...

Страница 45: ...1 4 C and the temperature of the accumulator s lower part meas 11 is above Accumulator Upper part MIN Accumulator Upper part hysteresis and the temp of the accumulator s lower part meas 11 exceeds the...

Страница 46: ...set to a higher level and the capacity for the hot domestic water increases The activated time for the switch HW Extra heating time can be set in the set values Freezing alarm In the freezing alarm ca...

Страница 47: ...ement 12 has reached controller indicated H1 supply water temperature 4 C and When HW Extra heat is activated and the temperature of the measurement 11 has reached the Hot water HW Extra heat The comp...

Страница 48: ...55 C When the temperature of the lower part of the boiler meas 10 is exceeded this setpoint always stops the compressor even if the top of the boiler commands the compressor to start Boiler Top hyste...

Страница 49: ...ches ON according to the Boiler Top temperature when meas 10 is lower than Boiler Top setting Hot water hysteresis Boiler Top hysteresis heating resistor The electrical heating resistor switches OFF a...

Страница 50: ...om Inputs and Outputs menu Delay function of radiator heating Outd temp delay on temp drop 0 0 0 15 h Outdoor temperature delay is in use if the radiator heating is se lected as a heating mode in the...

Страница 51: ...is automatically raised for 20 days The function is turned on automatically when the average daytime temperature has been more than 7 C for a minimum of 20 days and then falls below 7 C The function r...

Страница 52: ...unt of difference between measured supply water tempera ture and the supply water temperature set by the controller that causes an alarm when the deviation has continued for the entry delay time A dev...

Страница 53: ...at 100 I time 14 5 300 s The deviation in the supply water temperature from the set value is corrected by P amount in I time D time 0 0 100 s Regulation reaction speed up in the event of a temperatur...

Страница 54: ...ckup that it has created Software updates S203 memory card The controller automatically creates backup every hour to the con troller s internal memory and also to the memory card if the control ler ha...

Страница 55: ...no electricity Open the front cover screws and remove the front cover Release the display unit by pressing down firmly supports If required use a sharp weapon Detach the display unit carefully by pryi...

Страница 56: ...sed on line control room for professional remote control and monitoring optional Local Web Server remote control and monitoring M LINK optional Use of a GSM phone requires that the GSM modem optional...

Страница 57: ...formational H1 Setting values H2 Setting values The most important setting values are shown in the reply message You can change the setting values by modifeing the text message and sending it back to...

Страница 58: ...The modem s indicator light shows what mode it is in Inserting the SIM card Press the small black SIM card release button with for example a pen tip Part of the SIM card slot will stick out of the mo...

Страница 59: ...parately from other waste to prevent damage caused by uncon trolled waste disposal to the environment and the health of fellow human beings The users must contact the retailer responsible for having s...

Страница 60: ...ching current 1 5 mA inputs 27 and 28 switching current 0 5 mA inputs 25 and 26 Transfer resistance max 500 closed min 11 k open Analog outputs 53 54 64 66 68 70 Output voltage range 0 10 V Output cur...

Отзывы: