40
SUM ALARM
Output
Name
Selection
Information about alarm classes
Y4 (66 ja 67)
Sum alarm
1-class
2-class
3-class
1-, 2- or 3class
1- or 2-class
2 -or 3-class
1- or 3-class
Class 1 is for alarms classified as urgent that should al-
ways be immediately forwarded. These include freezing
risk alarms, pump alarms or sensor fault in supply water.
Class 2 includes e.g. room and outdoor temperature
sensor fault alarms.
When a sum alarm is activated, the 10VDC control is
activated (connector 66).
Renaming
Name of meas.:
Approve: Press OK a number of secons
Cancel: Press ESC a number of secons
e n e
r a
l
c o
n
m
s
p
a
e
Navigate to ”Name of measurement” and press OK. A naming dialogue will open. Turn
the selection knob and accept a letter by pressing OK.
Continue to the next input field by pressing OK.
Return to the previous input field by pressing ESC.
Press OK for extended period of time to accept.
Press Esc for extended period of time to exit without saving any changes.
G
ACTUATOR CONTROLS
Name
Output
Actuator selection
Running time / factory setting (setting range)
H1
Actuator control
AO1
AO1
0-10 V / 2-10 V /
10-0 V / 10-2 V/
3-point (TR1, TR2 )
Running time open ____ 150 s (10...500 s)
Running time close ____ 150 s (10...500 s)
H2
Actuator control
AO3
AO3
0-10 V / 2-10 V /
10-0 V / 10-2 V
Running time open ____ 150 s (10...500 s)
Running time close ____ 150 s (10...500 s)
DHW
Actuator control
Geopro SH:
Distribution
vave, actuator control
AO5
AO5
TR5, TR6
TR5, TR6
0-10 V / 2-10 V
10-0 V / 10-2 V
3-point (TR5, TR 6)
3-point (TR5, TR 6)
Running time open ____ 15 s (10...500 s)
Running time close ____ 15 s (10...500 s)
H1
Actuator control 2
(serial driving)
AO2
AO2
0-10 V / 2-10 V
10-0 V / 10-2 V
Running time ____ 150 s (10...500 s)
H2
Actuator control 2
(serial driving)
AO4
AO4
0-10 V / 2-10 V
10-0 V / 10-2 V
Running time ____ 150 s (10...500 s)
DHW
Actuator control 2
(serial driving)
AO6
AO6
0-10 V / 2-10 V
10-0 V / 10-2 V
Running time ____ 15 s (10...500 s)
PUMP CONTROLS
Name
Output
Control mode
Manual control
Attention!
P2
Pump control (H1)
TR3
Automatic
Manual ->
Stop
Run
An auxiliary relay with a coil volt-
age of 24 Vac should be used in
pump connection.
P3
Pump control (H2)
TR4
Automatic
Manual ->
Stop
Run
An auxiliary relay with a coil volt-
age of 24 Vac should be used in
pump connection.