3.3.
3.3.
Examplery Oil supply diagram
Examplery Oil supply diagram
3.3.1
3.3.1
Oil supply diagram
Oil supply diagram
25 - double closing valve (accessory)
A - Oil from tank
B - Return line to tank
C - Oil from pumping unit
D - Pressure regulating valve
The oil throughput from the pumping unit must be at least 1,2 x quantity of oil to be burned
kg/h + 150 kg/h
Example
If
If
Then
Then
burner capacity is 200kg/h
throughput must be
1,2 x 200 kg/h + 150 kg/h = 390 kg/h
Pay attention to instructions from the pump manufacturer when
dimensioning the pipeworks.
M
M
A
ZA
B
C
D
PI
PI
PI
TI
PS
PS
25
B-552E_1
RPMARINES 30820641GB