A - adjusting key (under cover)
.
B - release lever
.
C - adjusted at the factory, DO NOT RELEASE THE SWITCH!
.
D - scale indicates only the turning angle of servomotor shaft
.
With the release lever B the cam shaft can be disengaged. This makes it possible to
turn the cam discs manually.
Difference between switches IV and V must be approx. 3 - 5° The black
scale is in use. Cam switches VI, VII, and VIII are free ASZ
(potentiometer) in use when necessary
Do a flue gas analyzis to verify adjustments
Do not release the switch C. Change in position of cam discs will
damage servomotor and change burner adjustments.
38 (77)
RPMARINES 30820641GB
4. First start-up and adjusting