![Oilon RP-130 M Скачать руководство пользователя страница 22](http://html1.mh-extra.com/html/oilon/rp-130-m/rp-130-m_operation-and-maintenance-manual_3606597022.webp)
1
Lockout
Flame signal has not
been received during
safety time.
Every flame signal
failure after safety
time sequence leads
to a lockout
1
Lockout
Return line pressure
switch (max)
triggering stops fuel
injection.
Pressure switch is
optional component.
May not be included
to delivery.
|
Lockout
The flame signal has
been lost during
burner operation
If the wire link B has
been cut from the
plug section of the
control unit, repetition
of startup sequence
follows
|
Lockout
Air pressure signal
lost during operation
2.6.3
2.6.3
Restart
Restart
The control unit can be reset immediately after a lockout has occurred. After resetting (as
well as after correction of a fault, which resulted in a controlled shutdown, or after each
mains failure) the sequence switch always returns to its start position, whereby only
terminals 7, 9, 10 and 11 receive voltage in accordance with the control program. It is only
then that the control unit begins with a new burner start-up.
Do not keep the reset button pressed for more than 10 seconds.
22 (77)
RPMARINES 30820641GB
2. Burner operation