10090943EN
CONDITION
POSSIBLE CAUSE
REMEDY
7. Combustion
head
Inside oily or has heavy
carbon
deposits
Distance between diffuser disc
and nozzle incorrect
Incorrect combustion air
adjustment
Nozzle wrong sized or of wrong
type
Nozzle worn
Adjust
Adjust
Replace as appropriate
Replace
8. Other possible causes
Control unit goes to lock-out
Boiler smoke damper is closed
Boiler or chimney is blocked
Boiler room not adequately
ventilated
Adjust
Clean
Add supply of air
No smoke comes out of
chimney, only bluish smoke
and heat noticeable as a
rippling effect at the
chimney mouth. An oily
smell in the yard.
Excessive air supply
Adjust
Dark, oil-bearing smoke is
coming out of chimney
Not enough air to support
combustion
Adjust