25
10090943EN
8. Control Unit BHO 64.A/LOA 24.173A27
8.1. Time Sequence Diagram (Control Program)
Legend
TZ Limit
thermostat
TS Regulating
thermostat
E1 Preheater
TSW Preheater
thermostat
M1
Burner motor (fan/oil pump)
T1 Ignition
transformer
EV1
Solenoid valve 1
EV2
Solenoid valve 2
B1
Flame detector/flame signal
FR Flame
relay
BHO 64.A
LOA 24.173A27
tw
Heating up time of oil preheater (from cold
condition) up to connecting of contact ”TSW”
approx. 1 min
approx. 1 min
t1
Pre-purge time
approx. 13 s
approx. 13 s
t3
Pre-ignition time
approx. 13 s
approx. 13 s
t3n
Post-ignition time (control from terminal 6)
approx. 15 s
approx. 20 s
t3n
′
Post-ignition time (control from terminal 7)
approx. 2 s
approx. 2 s
t2
Safety time
max. 10 s
max. 10 s
t4
Interval between detection of flame and
release of terminal 5
approx. 15 s
approx. 20 s
---
Reaction time on loss of flame
< 1 s
< 1 s
A'
Commencement of start-up with burners with oil preheater.
A
Commencement of start-up with burners without preheater.
B
Time, when flame is detected (burner started).
C
Control unit (burner) in normal operating position (control program has ended).
D
Controlled shut-down by control thermostat TS
Required input signals to control unit
Control signals from control unit
Содержание Junior Pro 1 J10
Страница 2: ......
Страница 4: ......
Страница 8: ...4 10090943EN 3 Burner Technical Data 3 1 Exploded View Junior Pro 1 LJ10 ...
Страница 36: ......
Страница 37: ......
Страница 38: ......
Страница 39: ......
Страница 40: ......
Страница 41: ......
Страница 42: ......
Страница 43: ......
Страница 44: ......