![Oilon Junior Pro 1 J10 Скачать руководство пользователя страница 33](http://html1.mh-extra.com/html/oilon/junior-pro-1-j10/junior-pro-1-j10_operating-and-maintenance-instructions-manual_727275033.webp)
29
10090943EN
10. Fault Conditions and Procedures
In the event of fault conditions the basic requirements for correct operation must be first
examined:
1. Is the signal lamp indicating the readiness for running going on (burner switch in position
”operation”)?
2. Check, that fuse is not blown or loose.
3. Check the electric supply.
4. Check that all regulating and control devices are correctly set.
5. Are the safety devices in normal operating condition?
6. Is the burner getting fuel, are the valves in fuel line open, is there oil in the tank?
When it is established, that the fault is not due to above mentioned, the individual burner
functions must be checked. Reset the burner control unit if it is in lock out position (the signal
lamp is lit). Burner starts. Observe the burner functions. Measuring instruments can be used
while finding the fault.
CONDITION
POSSIBLE CAUSE
REMEDY
1. Motor
Burner motor does not
start
Faulty motor
Faulty control unit
Faulty preheater on LJ-burners
Replace
Replace
Replace
2. Ignition
failure
Burner motor starts,
control voltage from control
unit to ignition transformer
is switched on, no ignition
and after a short time
burner goes to lock out.
Dirty or worn ignition electrodes.
Insulator cracked
Ignition electrodes wrong
positioned
Incorrect setting of nozzle
distance
Damaged or loosened ignition
cable
Faulty ignition transformer
Clean or replace
Adjust according to instructions
Adjust according to instructions
Replace or fix
Replace
3. No flame establishment
Burner motor starts,
ignition is in order, after a
short time burner goes to
lock
out.
Nozzle does not supply oil
Solenoid valve does not
function:
- faulty solenoid valve or coil or
cable damaged
-
faulty control unit
Atomizing pressure of oil is too
low
Blocked or worn nozzle
Blocked preheater
(”LJ” burners)
Replace faulty part
See chapter ”4 Oil pump”
Replace
Replace
Содержание Junior Pro 1 J10