Installation & Operation Manual Merlin 2000S
2000S
IOM
Rev: 01 01-22
7
Fan Switch Integration
There is the facility to connect a Fan Switch.
A fan switch (Merlin FS1 or FS2 - sold separately) provides the facility to turn on fan(s) when the
2000S panel is switched on and removes power to fan(s) when the switched off.
There is a switch located on the circuit board labelled [EM SEL].
OFF
Instructs the system to shut down fan(s) and gas supply upon
activation of emergency shut off button(s). (Default)
ON
Instructs the system to leave the fans on and shut off the gas supply
only upon activation of emergency shut off button(s).
Note: This option is not available if a Fan Switch is not installed.
Fire Panel Integration
The Merlin 2000S can be integrated with a fire alarm to close the gas supply automatically in
the event of a fire. The volt free fire alarm signal can be wired in series with any remote
emergency shut off buttons.
If there are no remote emergency shut off buttons being installed, wire this directly to the
terminal marked [EM REMOTE].
Gas Fill Time and Prove Time
FILL TIME:
Amount of
time the gas valve opens to fill the gas line on power up or reset.
PROVE TIME:
Amount of time the system tests the gas line for leaks on power up or reset.
There are two switches located on the circuit board labelled [FILL TIME] and [PROVE TIME].
FILL TIME
PROVE TIME
OFF
5 Seconds (Default)
OFF
30 Seconds (Default)
ON
10 Seconds
ON
50 Seconds
Once the settings have been changed - remove power for 10 seconds.
Specification
Model:
2000S
Visual Indication
LED
Mains Electrical Power Input
100-240VAC
Gas Solenoid Valve Output
100-240VAC
Current Consumption
12W max (50mA)
Internal Fuse
3.15A
Pressure Sensor Operating Pressure
0 -10Kpa
Operating Temperature
32
–
104°F 0-95%RH Non-Condensing
Audible Alarm Buzzer dB
65 dB (300mm distance in quiet conditions)
Housing Material
Polylac PA-765
Approvals
CE, RoHS
O/All Dimensions (H x W x D) mm / inch
7.08 x 10 x 3.03”