Installation & Operation Manual

Merlin 2000S 

 

2000S

 

IOM

 

Rev: 01    01-22

 

4. BMS OUTPUT

Connections are available on the board for Building Management Systems. 
[NO Normally Open] [COM Common] [NC Normally Closed] 
These are volt free connections. 

This is a relay that changes state in alarm or when the gas is on/off and can be used in 
conjunction with the 12V DC output and other external relays that affect other devices and 
controls such as purge fans and audible alarms etc. 
See section; Switch Settings - for BMS options 

6. EM REMOTE

Connections for remote emergency shut-off or stop buttons is detailed on the circuit board as 

[EM REMOTE]. This is linked out as a factory setting.  

7. GAS DETECTOR

Connections can be made for a Merlin gas detector (LPG, NG, CO or Hydrogen). 
If no detector is being used leave the factory fitted link in.  
A wiring example is shown. 

Refer to your gas detector manual for further information. 

8. FAN SWITCHES

This terminal switches when the key is turned on and off.  
This can be connected to a fan switch (supplied separately) which can provide power to fans 
when the control panel is switched on. 

Screw the pressure sensor into the downstream port of your gas solenoid valve. 

Pressure sensors should be screwed to the downstream port of the valve.

 

Pressure Sensors are tested and certified to AS 4628/2005.

 

The pressure sensor is wired to the [PRESSURE SENSOR] connector and screwed into the downstream 
port of the gas solenoid valve. 

Connect the pressure sensor as shown: 

The sensor will monitor the gas supply pressure and if pressure drops below 0.5 or 1.2Kpa 

 

the gas valve will close.

 *

Maximum 100 Meters wiring distance from panel 

See section; Switch Settings - for Pressure options 

4. BMS OUTPUT

Connections are available on the board for Building Management Systems. 
[NO Normally Open] [COM Common] [NC Normally Closed] 
These are volt free connections. 

This is a relay that changes state in alarm or when the gas is on/off and can be used in 
conjunction with the 12V DC output and other external relays that affect other devices and 
controls such as purge fans and audible alarms etc. 
See section; Switch Settings - for BMS options 

5

.

  Pressure Sensor

Содержание Merlin 2000S

Страница 1: ...retain for future use This panel is designed for use when the kitchen appliances do not have flame failure devices fitted therefore gas proving is a requirement The Merlin 2000S system acts as an inte...

Страница 2: ...Mounting 3 Typical Installation Arrangement 4 Terminal Connections 4 Switch Settings 6 Specification 7 OPERATION 8 First Power Up 8 Emergency Shut Off Button 8 LED Indicators 8 Servicing General Main...

Страница 3: ...open the gas solenoid valve If the fans should fail the fan fail LED on the panel will illuminate and the gas solenoid will close The Merlin 2000S can work in conjunction with carbon dioxide natural g...

Страница 4: ...ied from the VALVE OUT connector using a 3 core cable can be connected to a gas solenoid valve which can shut the gas supply on alarm status Pressure sensors should be screwed to the downstream port o...

Страница 5: ...f This can be connected to a fan switch supplied separately which can provide power to fans when the control panel is switched on Screw the pressure sensor into the downstream port of your gas solenoi...

Страница 6: ...various DIP switches on the front circuit board that can be adjusted to configure your system as per the following Auto Reset There is a switch located on the circuit board labelled AUTO RESET OFF Whe...

Страница 7: ...in series with any remote emergency shut off buttons If there are no remote emergency shut off buttons being installed wire this directly to the terminal marked EM REMOTE Gas Fill Time and Prove Time...

Страница 8: ...on the Merlin 2000S will open the gas valve and the Gas On LED will illuminate ON Gas On OFF Gas Off Testing This LED will illuminate for approximately 30 seconds when the panel is checking the integr...

Страница 9: ...external Merlin detector connected detects high levels of gas this LED will illuminate and the Gas valve will turn off OFF OK ON Gas detected CO2 High Under normal working conditions this LED is off...

Страница 10: ...safely If the bump test results are not within the acceptable range the gas detector must not be used until a full calibration has been conducted Bump testing has a number of benefits for the end use...

Страница 11: ...pering or other causes not arising from defects in material or workmanship This warranty extends to the original consumer purchaser of the product only Warranty disclaimers Any implied warranties aris...

Страница 12: ...o the system owner or system user Date of Installation Installation Location Organisation Stamp Signature of the installer www oceaniagassafety com Oceania Gas Safety Tuakau Waikato New Zealand 642123...

Отзывы: