Installation & Operation Manual Merlin 2000S
2000S
IOM
Rev: 01 01-22
9
•
Extract Fans
Under normal working the LED will illuminate.
If an extract fan fault is detected, the LED will flash.
ON = OK / *FLASHING = One of the extract fans is not running
*IF SUPPLY AND/OR EXTRACT FANS LED FLASHES FOR MORE THAN 20 SECONDS, THE GAS WILL SHUT OFF.
•
Fan Fault
Under normal working conditions this LED is off.
If a fan fault is present for more than 20 seconds, the LED will illuminate RED.
OFF = OK / ON = the gas supply has been shut off due to a ventilation fault.
•
EM Stop
If an emergency shut off button (either remote or on the panel) is pressed, the LED will
illuminate and the gas is shut off. The button(s) must be re-set before restarting the system.
OFF = OK / ON = Emergency Shut Off button pressed
•
Gas Detected
Under normal working conditions this LED is off.
If an external Merlin detector connected detects high levels of gas this LED will illuminate and
the Gas valve will turn off.
OFF = OK / ON = Gas detected.
•
CO
2
High
Under normal working conditions this LED is off.
If the concentration of Carbon Dioxide (CO
2
) in the air is at alarm level (CO2 Monitors sold
separately), the LED will show illuminate and the Gas valve will turn off.
OFF = OK / ON = the concentration of CO
2
is at alarm level.
Servicing & General Maintenance
✓
DO carefully remove any accumulated dust from the outer enclosure once a month.
NEVER spray lighter gas, paint or other aerosols near detectors or monitors.
NEVER paint the device. Paint will seal vents and may interfere with the device.
It is recommended that any detectors connected to the system are inspected and serviced
at least annually from the date of installation for optimum performance and protection.
Avoid exposure of high concentrations of alcohol found in many products, this can damage,
deteriorate or affect gas detectors. For more information refer to your detector manual.