Installation & Operation Manual                                                                                        Merlin 2000S 

 

 

 

 

2000S

 

IOM

 

Rev: 01    01-22

 

 

INSTALLATION 

   Planning 

 

This panel is designed for use when the kitchen appliances do not have flame failure devices 
fitted, therefore gas proving is a requirement. 
The Merlin 2000S system acts as an interlock between the ventilation system and the gas 
solenoid valve. The system is compatible with both current monitors and air pressure 
differential switches in order to interlock with up to 4 fans. 

 
The fans can be monitored through air pressure switches or by means of an additional current 

monitor. To operate the Merlin 20

00S the fans should be turned to the ‘on’ position, once the 

panel receives a signal to indicate the fans are operating the key on the panel can be turned 

to the ‘on’

 

position and this will open the gas solenoid valve. If the fans should fail, the ‘fan fail’ 

LED on the panel will illuminate and the gas solenoid will close.  
 
The Merlin 2000S can work in conjunction with carbon dioxide, natural gas, carbon monoxide 
and LPG sensors.  
 

 

 

   Fixing - Mounting 

 

Unpack all the parts! 

 

 

1.

 

Carefully remove the front cover from the unit by unscrewing the four bolts located at each 
corner. To do this 

 use the socket wrench provided. 

 

2.

 

Mark the four screw holes located on the back of the enclosure to the wall. Ensure the wall 
surface is flat to prevent base distortion. 

 

3.

 

After executing the mounting and the connections 

 replace the front cover and insert the 

security caps over the four bolts. 

 

 

 

 

Please refer to your detector manual for important information regarding coverage, 

location and positioning including areas and conditions to avoid. 

 

 

Be careful when creating access for cables 

 Damage to boards will void any warranty. 

Carefully remove the circuit board before drilling cable entry holes.

 

Содержание Merlin 2000S

Страница 1: ...retain for future use This panel is designed for use when the kitchen appliances do not have flame failure devices fitted therefore gas proving is a requirement The Merlin 2000S system acts as an inte...

Страница 2: ...Mounting 3 Typical Installation Arrangement 4 Terminal Connections 4 Switch Settings 6 Specification 7 OPERATION 8 First Power Up 8 Emergency Shut Off Button 8 LED Indicators 8 Servicing General Main...

Страница 3: ...open the gas solenoid valve If the fans should fail the fan fail LED on the panel will illuminate and the gas solenoid will close The Merlin 2000S can work in conjunction with carbon dioxide natural g...

Страница 4: ...ied from the VALVE OUT connector using a 3 core cable can be connected to a gas solenoid valve which can shut the gas supply on alarm status Pressure sensors should be screwed to the downstream port o...

Страница 5: ...f This can be connected to a fan switch supplied separately which can provide power to fans when the control panel is switched on Screw the pressure sensor into the downstream port of your gas solenoi...

Страница 6: ...various DIP switches on the front circuit board that can be adjusted to configure your system as per the following Auto Reset There is a switch located on the circuit board labelled AUTO RESET OFF Whe...

Страница 7: ...in series with any remote emergency shut off buttons If there are no remote emergency shut off buttons being installed wire this directly to the terminal marked EM REMOTE Gas Fill Time and Prove Time...

Страница 8: ...on the Merlin 2000S will open the gas valve and the Gas On LED will illuminate ON Gas On OFF Gas Off Testing This LED will illuminate for approximately 30 seconds when the panel is checking the integr...

Страница 9: ...external Merlin detector connected detects high levels of gas this LED will illuminate and the Gas valve will turn off OFF OK ON Gas detected CO2 High Under normal working conditions this LED is off...

Страница 10: ...safely If the bump test results are not within the acceptable range the gas detector must not be used until a full calibration has been conducted Bump testing has a number of benefits for the end use...

Страница 11: ...pering or other causes not arising from defects in material or workmanship This warranty extends to the original consumer purchaser of the product only Warranty disclaimers Any implied warranties aris...

Страница 12: ...o the system owner or system user Date of Installation Installation Location Organisation Stamp Signature of the installer www oceaniagassafety com Oceania Gas Safety Tuakau Waikato New Zealand 642123...

Отзывы: