14
OEG Pressure storage units DE / DZ
GB
Oil-feeding units are only allowed to be installed by specialised companies. These
operating instructions are exclusively intended for the specialist.
All corresponding regulations as well as the operating instructions of the boiler and
burner manufacturers are to be observed.
If the installation of an anti-siphon valve in the suction pipe is necessary as the maximum
oil level of the heating oil tank is above the unit, an electrically controlled solenoid valve
being used is to be connected in parallel to the integrated solenoid valve of the suction
port. The maximum connected load of 100 VA is to be considered here. When using
solenoid valves with high power consumption, a relay should be used.
Medium
Heating oil EL
Heating oil EL, low-sulphur
Other media on request
Dimensions
DE600 – DE1200:
410 x 280 x 600 mm (L x W x H)
DZ600 – DZ1200:
450 x 240 x 540 mm (L x W x H)
DE3200 – DE12000: 700 x 400 x 730 mm (L x W x H)
DZ3200 – DZ12000: 700 x 400 x 730 mm (L x W x H)
Motor
DE600 / DE1200 / DZ600 / DZ1200:
0.09 kW, 230V, 0.95A,
2800 rpm
DE3200 / DZ3200:
0.25 kW, 230V, 2.00A,
2800 rpm
DE6000 – DE12000 / DZ6000 – DZ12000: 0.37 kW, 400V, 0.95A,
2800 rpm
Protection degree IP54
Technical data
11.0
Type
Electrical
connection
Max. total burner
output
Capacity of diaphragm
expansion vessel
Pipe
connections
Weight
DE600
230V
Schuko plug
600 kW
5 litres
3/8"
25.5 kg
DE1200
230V
Schuko plug
1,200 kW
5 litres
3/8"
26 kg
DZ600
230V
Schuko plug
600 kW
5 litres
3/8"
48 kg
DZ1200
230V
Schuko plug
1,200 kW
5 litres
3/8"
48 kg
DE3200 /
DZ3200
230V
Schuko plug
3,200 kW
18 litres
3/4"
52/64 kg
DE6000 /
DZ6000
400V CEE,
16 A
6000 kW
18 litres
3/4"
54/66 kg
DE12000 /
DZ12000
400V CEE,
16 A
1,2000 kW
18 litres
3/4"
54/66 kg