Multi-functional DC inverter air/water heat pump
GB
Parameter table for system setting
Parameter modification
4.9
P00
ON/OFF
0: OFF 1: ON
0
0
0
0
P01
Working mode
0~4
0-DHW 1-A/C Heating 2-A/C Cooling
3-DHW+A/C Heating 4-DHW+A/C
Cooling
1
1
1
1
P02
Target temperature Heating
10~60 °C
45
45
45
45
P03
Target temperature Cooling
10~30 °C
12
12
12
12
P04
DHW target temperature
10-60°C (value ≥ P35, only electrical heater)
50
50
50
50
P05
Target temperature space
18~35 °C
21
21
21
21
P06
A/C temperature difference
1~15 K
5
5
5
5
P07
DHW temperature difference
1~15 K
5
5
5
5
P08
A/C heating AU curve
max. temperature
(weather-compensated AU curve)
35~50 °C
45
45
45
45
P09
A/C heating AU curve
parallel shifting value
(weather-compensated AU curve)
-10~10 °C
0
0
0
0
P10
Thermal disinfection cycle (days)
1-99 days
7
7
7
7
P11
Thermal disinfection start time
1-23 (time)
23
23
23
23
P12
Thermal disinfection runtime
5-99 min.
10
10
10
10
P13
Thermal disinfection temperature
50~75 °C
70
70
70
70
P14
Thermal disinfection mode
selection
0-Auto 1-manual 2-OFF
0
0
0
0
P15
Night mode starting point
0-23 (time)
22
22
22
22
P16
Night mode ending point
0-23 (time)
6
6
6
6
P17
Night mode OFF/ON
0-OFF 1-ON
0
0
0
0
P18
DHW AU OFF/ON
0-OFF 1-ON
0
0
0
0
P19
A/C AU OFF/ON
0-OFF 1-ON
0
0
0
0
P20
Working mode circulation pump
0-without stop, 1-stop when temp.
has been reached, 2-runtime: 1
min. every 15 min.
0
0
0
0
P21
Frost protection interval
circulation pump
5~50 min
30
30
30
30
P22
Ambient temp. to activate A/C
electrical heater
-30~20 °C
0
0
0
0
P23
Ambient temp. to activate DHW
electrical heater
-30~20
°C
0
0
0
0
P24
Electrical heater to activate the
temperature parallel shifting
value
1~15
°C
2
2
2
2
P25
A/C frost protection temperature
-15~5
°C
3
3
3
3
P26
Multi-control defrost interval
0~4
0-without defrost, 1~4 multiple
defrost interval time
1
1
1
1
P27
First defrost interval
15-99 min.
35
35
35
35
P28
Defrost cycle
0-Auto 1-Manual defrost (after
defrost back to standard 0)
0
0
0
0
P29
Coil temperature to activate
defrost
-8~5
°C
0
0
0
0
P30
Coil temperature to deactivate
defrost
5~30
°C
20
20
20
20
P31
Max. defrost time
2~20 min
15
15
15
15
P32
EEV control mode
0-no 1-test chart 2-manual
3-suction gas overheating,
4-discharge gas overheating
4
4
4
4
P33
EEV manual setting of opening
steps (Heating)
50-480 (only valid if P32=2)
400
400
400
400
P34
EEV manual setting of opening
steps (Cooling)
50-480 (only valid if P32=2)
400
400
400
400
P35
In DHW mode, highest water
temperature for running
compressor
0~60
°C
55
55
55
55
No
Description
Range
Standard
9KW
650 001 331
Standard
6KW
650 001 330
Standard
12KW
650 001 332
Standard
18KW
650 001 333