OPERATION | Making settings
14
www.ochsner.com | BIA-EUROPA Mini IWP-EN12
Symbol
Pa-
rame-
ter
Designation Description
LEG
Anti-legionel-
la mode
operating
program
off = anti-legionella mode is off
int = anti-legionella mode in-
terval program
date = anti-legionella mode
time program
off = default setting
hovr
Start time,
anti-legionel-
la mode
(interval pro-
gram)
Here you set the time when
anti-legionella mode should
start.
00:00 = default setting
day
Anti-legionel-
la mode
interval (inter-
val program)
The interval in days is set
here.
If, for example, anti-legionella
mode is to start every Satur-
day, then 7 days must be set
on a Saturday.
0 = anti-legionella mode deac-
tivated (default setting)
5day
1. Weekday
start time
(time pro-
gram)
The days for the start time are
defined here.
day1 = Monday to day7 =
Sunday
off = default setting
5 on
1. Start time
(time pro-
gram)
The time from which the op-
erating mode is enabled is set
here.
00:00 = default setting
6day
2. Weekday
start time
(time pro-
gram)
The days for the start time are
defined here.
day1 = Monday to day7 =
Sunday
off = default setting
6 on
2. Start time
(time pro-
gram)
The time from which the op-
erating mode is enabled is set
here.
00:00 = default setting
Pset
PA1
C52
Max. heat-up
time in an-
ti-legionella
mode
If the anti-legionella temper-
ature is not reached within
the time set here, the heating
cycle is terminated.
10h = default setting
Pset
PA2
C53
Max. waiting
time for an-
ti-legionella
mode
Password: System partner
password
If at the specified start time
anti-legionella mode is
blocked, the start of the heat-
ing cycle is delayed.
Anti-legionella mode is termi-
nated if the heating cycle does
not start within the time speci-
fied here.
4h = default setting
4.4.1 Time program
»
Press the Menu button.
In the main menu, the “DHW” symbol is displayed brightly.
»
Press the OK button to confirm.
»
To scroll in the DHW menu, use the Down button.
The symbols “DHW” and “Time” are displayed brightly. The
display text LEG is shown.
»
Press the OK button to confirm.
»
Use the Up button and Down button to change the
operating program.
date = anti-legionella mode time program
»
Press the OK button to confirm.