Plenum Duct
Kit Flange
2OACH12
2OACH18
2OACH24
2OACH36
2OACH60
2DCP
-
1
12
-
inch
✓
2DCP
-
2
12
-
inch
✓
✓
DCP
-
5
16
-
Inch
✓
✓
Maximum Approximate
Equivalent Feet
25
50
50
50
100
Estimated External
Static Pressure
(.20)
(.25)
(.25)
(.25)
(.50)
2DCP
-
1, 2DCP
-
2, DCP
-
5
To estimate the
“
equivalent feet
”
of condenser duct,
add the length of the condenser intake duct run and the length of the
condenser discharge duct run, and add 6 equivalent feet per bend in the
duct. Make sure that you do not exceed the rated E.S.P. to avoid shut
down due to the high pressure switch cut
-
out.
13
ACCESSORIES
CONDENSER RETURN AIR PLENUM
NOTE —
When installing the condenser return air plenum with a ceiling panel kit,
allow for a minimum separation distance of 2 feet between the unit discharge duct
and the return air duct. It is also recommended to direct the condenser discharge
Condenser return air plenums are available for installations where it is required to duct
air to the inlet of the condenser. The plenum easily fits into place on the back of the unit,
and is provided with a flange for connecting 12
-
inch or 16
-
inch flexible ducting. A
condenser return air plenum can substantially reduce air noise and allow the unit to
operate without drawing condenser air from the conditioned space. Refer to the table
below for configuration and application information.
Содержание 2OACH1811
Страница 26: ...24 PIPING SCHEMATIC...
Страница 27: ...25 WIRING SCHEMATIC FOR 2OACH12 18 and 24 DISCHARGE TEMP SENSOR...
Страница 28: ...26 WIRING SCHEMATIC FOR 2OACH3612 DISCHARGE TEMP SENSOR...
Страница 29: ...27 WIRING SCHEMATIC FOR 2OACH6012 DISCHARGE TEMP SENSOR...
Страница 31: ...29 WIRING SCHEMATIC FOR 2OACH3632 DISCHARGE TEMP SENSOR...
Страница 32: ...30 WIRING SCHEMATIC FOR 2OACH3634 DISCHARGE TEMP SENSOR...
Страница 33: ...31 WIRING SCHEMATIC FOR 2OACH6032 DISCHARGE TEMP SENSOR...
Страница 34: ...32 WIRING SCHEMATIC FOR 2OACH6034 DISCHARGE TEMP SENSOR...