MI SERIES
– Manual (v1.7)
Obelux Oy, Kutomotie 6 B, 00380 Helsinki FINLAND
© Obelux Oy 2017 Technical information in this document is subject to change without notice.
Page: 15(28)
RS-485 bus should be terminated with on-board 120 ohm resistors on both ends of this communications bus.
Turn on DIP4 on from the termination DIP switches. Location of the termination DIP switches can be seen in
Figure 6.