3
Heating Cable Repair
44
|
nVent.com
3.4
End Termination Procedure
Note
: Shield work area from environmental
factors such as wind as it will cool the joint
temperature making brazing difficult.
Remove insulation and banding from heating cable so
that 12 in (30 cm) of cable and end cap is accessible.
Ensure that the portion of the cable being worked on can
be moved away from the surface at least 4 in (10 cm) to
allow access when brazing (see repair jig in Appendix G).
Using the tube cutter, cut the corrugate 1/2 in (13 mm)
from the corrugate plug (ARO fitting). Once cut, turn the
plug counter-clockwise to unscrew the plug from the
heating cable end cap (Figure 53).
1/2”
(13mm)
Corrugate plug
Corrugate
Threaded rod
Turn corrugate plug
counter clockwise to
remove
Figure 53: Cut corrugate and unscrew corrugate plug
Using the tube cutter, cut off 12 in (30 cm) of the
corrugate (Figure 54). Save this 12 in (30 cm) piece of
corrugate for reuse later in this procedure.
12"
(30 cm)
Figure 54: Remove 12 in (30 cm) corrugate