Heating Cable Repair
nVent.com
|
41
Cool and clean the brazed joints. Use only the nylon
mesh sanding pad on the corrugate (Figure 48). Emery
cloth is too aggressive for the corrugate. If using water
to cool the joint, it is critical that no water gets inside the
repair sleeves and corrugate. Water inside the corrugate
can lead to corrosion and early failure of the sheath.
Note
: Always ensure all flux has been removed
from the corrugate to prevent corrosion. Hot water
may be used to remove the flux.
Nylon mesh sanding pad
Figure 48: Clean brazed areas
When the joints are clean and cooled, attach the air
fitting to the pressure port and pressurize the corrugate
to 5 psi minimum to 40 psi maximum (Figure 49).