Heating Cable Repair
nVent.com
|
17
Hot/hot joint:
Using the tube cutter, cut the corrugate
5 in (12.7 cm) back from both cut ends. Remove the cut
corrugate and discard (Figure 8).
Hot/cold joint:
Using the tube cutter, cut the corrugate
5 in (12.7 cm) back from the cut end. Remove the cut
corrugate and discard (Figure 9).
Figure 8: Cut and remove corrugate from both ends
Heating
cable
Cut and remove corrugate
from both ends
5”
(12.7cm)
5”
(12.7cm)
Figure 9: Cut and remove corrugate from MI
heating cable end
Cut and remove corrugate
from MI heating cable end
Cold lead
5” (12.7 cm)
Corrugate
MI heating
cable