23
Water Temp. & Programming
NOW
HOT WATER MAINTENANCE
BOILER
ECONOMY TEMP
AT 05:00 p.m.
NEXT
INFO, RESET, SERVICE, TEST....
CABLE TYPE, PIPE DAIMETER,...
COUNTRY, LANGUAGES, UNITS,...
APPARTMENT, MAINTAIN, ECONOMY,....
SETTING
SYSTEM
HEATING CABLE & PIPE
GENERAL SETTINGS
WATER TEMP. & PROGRAM
INFO
TEST PROGRAM
RESET
SERVICE
STATUS
SYSTEM
SELECT LANGUAGE
SELECT COUNTRY
SELECT DATE
SELECT TIME
SELECT ALARM
GENERAL SETTING
SELECT SAVING TIME
ENGLISH
UNITED STATES
01.10.2017
14 : 17
OFF
ON
14 : 17
14 : 17
14 : 17
14 : 17
02:14 p.m.
SELECT WATER TEMPERATURE
SELECT PROGRAM
PROGRAM TIMER
WATER TEMP. & PROGRAM
131°F/122°F
14 : 17
HOTEL
SELECT CABLE TYPE
SELECT PIPE DIAMETER
SELECT INSULATION THICKNESS
SELECT AMBIENT TEMPERATURE
SELECT BOILER SENSOR
SELECT BOILER CUT-OFF TEMPS.
HWAT-R2
DN 25
40 MM
20 °C
ON
35/85 °C
HEATING CABLE & PIPE
140 °F
131°F
131°F
Maintain /
Economy
temperature
The maintain temperature is the water temperature that
you set for normal use. The minimum temperature is
98
°F
(
37
°C) or the economy temperature, whichever is
higher. The maximum temperature depends on cable type,
pipe thickness, insulation thickness and ambient
temperature. The economy temperature is the water
temperature for periods in which the amount of hot water
used is low (at night) or high (peak period). Select the
temperature using the + / - keys. The minimum temperature
is
98
°F (
37
°C) for use in environments such as schools, and
105
°F (
41
°C) in the Apartments program. The maximum
temperature is the selected maintain temperature.
Building type
program
The HWAT-ECO-GF has
7
default timer programs. Select
by tapping on the program of choice (box will turn red).
See figure xx for the schedule of each program.
The building program reflects the tapping profiles.
Timer
schedule
Graphically program the Timer in
1
hour time blocks.
You can set a block to OFF, Economy temp,
Maintain temp, or HEAT-UP*
OFF
MAINTAIN
HEAT-UP
ECONOMY
(*HEAT-UP=
158
°F [
70
°C] or
100
% power (when the power
can’t reach
158
°F [
70
°C] ) only when using the HWAT-R
2
or HWAT-P
1
cable. This is the legionella control mode
and it is not pre-programmed. Activate this preferably
during night hours to minimize risk of scalding. Use the
modes button to overwrite the timer schedule. Select a
temperature mode to assign to the time bock of choice.
5
. PARAMETER SETTINGS (DEFAULT)
Language
English
Country
Not pre-defined; to be selected
Date
--/--/
2022
or last saved date
Time
00
:
00
; or last saved time
Building program
Not pre-defined; to be selected
Heating cable type
Not pre-defined/ to be selected
Pipe diameter
1
" (DN
25
)
Insulation thickness
1
"
Maintain temperature
HWAT-R
2
131
°F (
55
°C)
HWAT-P
1
122
°F (
50
°C)
Economy temperature
HWAT-R
2
122
°F (
50
°C)
HWAT-P
1
113
°F (
45
°C)
Low temperature limit
95
°F (
35
°C)
High temperature limit
HWAT-R
2
185
°F (
85
°C)
HWAT-P
1
149
°F (
65
°C)
Alarm sound
ON
Key lock
OFF
Содержание HWAT-ECO-GF
Страница 2: ...2 nVent com RAYCHEM EN FR...
Страница 7: ...nVent com RAYCHEM 7 EN FR 2 INSTALLATION INSTRUCTIONS 1A 1B 5 2 150 mm...
Страница 8: ...8 nVent com RAYCHEM EN FR 3 4 5 1 2 A B C...
Страница 14: ...14 nVent com RAYCHEM EN FR 11 CLICK...
Страница 15: ...nVent com RAYCHEM 15 EN FR 12 13 14 MAX C30A CB ON...