8
RAYCHEM-OM-EU1838-ELEXANT450c-ML-2103
FACTORY SETTINGS (DEFAULT)
Language
English
Country
None; To be selected
Date
01
/
01
/
2018
or last saved date
Time
00
:
00
or last saved time
Operation mode
To be selected
Heating cable type
To be selected
Pipe diameter
DN
25
Insulation thickness
30
mm
SET temperature
+
3
°C
Minimum ambient temperature
–
15
°C
Heating in sensor failure mode
ON
Low temperature limit
–
40
°C
High temperature limit
+
85
°C
Low temperature alarm
0
°C
High temperature alarm
+
65
°C
Alarm sound
OFF
Key lock
ON
ERROR / ALARMS AND TROUBLESHOOTING
Error Code
Elexant
450
C
Remedy
E:
2
.
1
SENSOR_
1
_OPEN
Check sensor connection
E:
2
.
2
SENSOR_
1
_SHORT
Check sensor and replace it
E:
2
.
3
SENSOR_
2
_OPEN
Check sensor connection
E:
2
.
4
SENSOR_
2
_SHORT
Check sensor and replace it
E:
3
.
1
SENSOR_
1
_TEMP_HIGH
Sensor
1
High temperature alarm
E:
3
.
2
SENSOR_
2
_TEMP_HIGH
Sensor
2
High temperature alarm
E:
4
.
1
SENSOR_
1
_TEMP_LOW
Sensor
1
Low temperature alarm
E:
4
.
2
SENSOR_
2
_TEMP_LOW
Sensor
2
Low temperature alarm
E:
5
n/a
E:
6
.
0
n/a
E:
6
.
1
INTERNAL_ERROR
Replace unit
E:
6
.
2
INTERNAL_ERROR_RTC
Replace unit
E:
6
.
3
INTERNAL_ERROR_PM
Replace unit
E:
6
.
4
INTERNAL_ERROR_ADC
Replace unit
E:
6
.
5
INTERNAL_ERROR_IP
Replace unit
E:
6
.
6
n/a