PARAMETER SETTINGS

System

Information

General info about the unit name, commissioning date, firmware version, nVent contact 

info per country and unit serial number.

Test program

Test program

YES:

The test program runs for 

30

 minutes, during which all parameters will be ignored to 

check the heating cable and the connection on site. You can stop the test program  

at any time.

NO:

 Back to main menu settings

Reset

Confirm:

Activate the Quick install menu and return all settings to factory settings.
Quickstart process restarts automatically.

Cancel: 

Back to main menu settings

Service

Access for nVent service team

Status

Info on current status of the control unit:
Sensor 

1

:  Open/short or temperature value

Sensor 

2

 : Open/short or temperature value

SET Point temperature : Value in °C
Duty cycle: Value will be displayed only in PASC mode
Operation mode: LINE / PASC (heating circuit 

1

 / heating circuit 

2

)

Key lock

The unit´s parameter input can be protected by a key lock 

KeyLock

Access code: 

3000

When key lock is “On”, the setup and timer menus’ are protected by password. 
The unit can be unlocked by entering the pre-defined password (

3000

).  

After 

10

 minutes of inactivity on screen or when Lock “on” key is pressed, the unit will 

automatically lock itself. 
To deactivate the Key lock function, enter code 

3000

 and activate “OFF”.

Key lock code cannot be changed.

Heating Cable & Pipe

Heating 

zone 

1

Example

Heating 

zone 

2

Example

Parameters

Note

Mode

ON

/ ON

AMBIENT Sensor: ON/OFF
LINE Sensor: ON/OFF
Default:---

Heating circuit 

1

: ON ; OFF

Heating circuit 

2

: ON ; OFF

Default: ---

Individual adjustments per heating zone.
Assign a sensor to each heating zone by 

activating check mark.
AMBIENT: Ambient temperature 

measurement by PASC – proportional 

ambient temperature measurement. Energy 

saving mode; recommended for multiple 

pipe segments.
LINE: Pipe temperature measurement.

Set point

+

3

°C

/ +

3

°C

NTC Sensor:
Range: 

0

°C to +

80

°C

PT

100

 Sensor (with sensor 

module SM-PT

100

-

2

)

Range: 

0

°C to +

245

°C

Default: +

3

°C

The set temperature is the temperature to 

ensure to protect the pipe from freezing or 

to maintain a certain pipe temperature.
Select the temperature using the + / – keys 

for each heating circuit zone individually.

Содержание Elexant 450c

Страница 1: ...Operation Manual Electronic Control Unit For Safe And Efficient Operation Of Pipe Freeze Protection Self Regulating Heating Cable Elektronische Steuereinheit f r einen sicheren und effizienten Betrie...

Страница 2: ...ANT450c ML 2103 TABLE OF CONTENTS PROGRAM START 3 PARAMETER SETTINGS 5 FACTORY SETTINGS DEFAULT 8 ERROR ALARMS AND TROUBLESHOOTING 8 INHALT PROGRAMMSTART 9 SOLLWERTEINGABE 11 WERKSEINSTELLUNGEN STANDA...

Страница 3: ...an internally calculated duty cycle LINE Pipe line temperature measurement Assignment of sensors Sensor 1 for heating circuit 1 sensor 2 for heating circuit 2 a revision of this assignment can be don...

Страница 4: ...CHEM 4 RAYCHEM OM EU1838 ELEXANT450c ML 2103 Main Screen SETTINGS KEYLOCK APPLICATION WARNINGS TIME SET TEMPERATURE HEATING ZONE 1 2 RELAY ON OFF SENSOR NUMBER OPERATION MODE ACTUAL TEMPERATURE APPLIC...

Страница 5: ...ey lock KeyLock Access code 3000 When key lock is On the setup and timer menus are protected by password The unit can be unlocked by entering the pre defined password 3000 After 10 minutes of inactivi...

Страница 6: ...Other system can be used if heating cable type is not known or listed Pipe diameter DN 25 DN 25 Range DN 10 DN 125 Default DN 25 Assign the correct pipe diameter per heating zone 1 and or 2 You can ch...

Страница 7: ...NO FI RU CZ PL SK LT Country Select a country in this menu Your selection defines the default values used for time format pipe diameter and insulation thickness and customer contact data Countries DE...

Страница 8: ...ound OFF Key lock ON ERROR ALARMS AND TROUBLESHOOTING Error Code Elexant 450C Remedy E 2 1 SENSOR_1_OPEN Check sensor connection E 2 2 SENSOR_1_SHORT Check sensor and replace it E 2 3 SENSOR_2_OPEN Ch...

Страница 9: ...nes definierten Arbeitszyklus zu betreiben ROHRF HLER Leitungsrohr Temperaturmessung F hlerzuordnung F hler 1 zu Heizkreis 1 F hler 2 zu Heizkreis 2 Die Zuordnung kann sp ter im Parametrierungsmen ge...

Страница 10: ...M 10 RAYCHEM OM EU1838 ELEXANT450c ML 2103 Hauptbildschirm EINSTELLUNGEN TASTEN SPERRE ANWENDUNG WARNUNGEN ZEIT SOLL TEMPERATUR HEIZZONE 1 2 RELAIS EIN AUS F HLERNUMMER BETRIEBSART AKTUELLE TEMPERATUR...

Страница 11: ...ugangscode 3000 Wenn die Tastensperre auf Ein steht sind die Men s Setup und Timer durch ein Passwort gesch tzt Das Ger t kann durch Eingabe des vordefinierten Passworts 3000 tempor r entsperrt werden...

Страница 12: ...ZH Heizbandreihe 10XL2 ZH 15XL2 ZH 26XL2 ZH 31XL2 ZH FS C10 2X Andere Systeme Standard W hlen Sie den Typ des in Ihrer Installation verwendeten nVent RAYCHEM Heizkabels das an Heizzone 2 angeschlossen...

Страница 13: ...ehler nicht ausgeschaltet Hysterese 2 K 2 K Bereich 1 5 Standard 2 K Hysteresewert kann oberhalb des Sollwerts ver ndert werden ALLGEMEINE EINSTELLUNGEN Sprache W hlen Sie Ihre Sprache aus dem Sprachm...

Страница 14: ...ARME UND FEHLERBEHEBUNG Fehlercode Elexant 450C Fehlerbehebung E 2 1 F hler 1 offen F hlerverbindung pr fen E 2 2 F hler 1 Kurzschluss F hler pr fen und austauschen E 2 3 F hler 2 offen F hlerverbindu...

Страница 15: ...605 01 88 salesee nVent com Italia Tel 39 02 577 61 51 Fax 39 02 577 61 55 28 salesit nVent com Lietuva Latvija Eesti Tel 370 5 2136633 Fax 370 5 2330084 info baltic nVent com Magyarorsz g Tel 36 1 25...

Отзывы: