RAYCHEM-OM-EU1838-ELEXANT450c-ML-2103

Heating Cable & Pipe

Heating 

zone 

1

Example

Heating 

zone 

2

Example

Parameters

Note

Heating in case of  

sensor error

ON

/ ON

Fail Safe: ON/OFF
Default: ON

In case of a sensor error (short/open)  

the heating output (Relay) can be  

switched OFF by activating a check mark 

per heating zone.
Default: ON; heating system will not be 

switched OFF in sensor failure mode.

Hysteresis

2

 K

2

K

Range: 

1

 - 

5

 

Default: 

2

K

Adjustable hysteresis above set point.

General Settings

Language

Choose your language from the language menu.

Languages:
EN; DE; NL; DA; FR; IT; SV; NO; FI; RU; CZ;  

PL; SK; LT

Country

Select a country in this menu. Your selection defines the 

default values used for time format, pipe diameter and 

insulation thickness and customer contact data.

Countries
DE; AT; CH; GB; FR; IT; PL; CZ; DK; SE; BE; 

RU; NO; LT; SK; NL; FI; IE

Date

Use the up/down arrow keys to select the year. 
After a power break of more than 

10

 days you need to  

re-enter the date.

Default: 

00

;

00

,

2018

Time

Use up/down arrow keys to set hour and minute.
After a power break of more than 

10

 days you need to  

re-enter the time.

Default: 

00

:

00

Alarm tone

An alarm tone will go off inside the unit indicating an error 

condition. Activate/deactivate the alarm tone by pressing 

ON/OFF. 

Note:

 Alarm messages will be displayed and the alarm 

relay will switch any time in case of a malfunction.

Default : OFF

Содержание Elexant 450c

Страница 1: ...Operation Manual Electronic Control Unit For Safe And Efficient Operation Of Pipe Freeze Protection Self Regulating Heating Cable Elektronische Steuereinheit f r einen sicheren und effizienten Betrie...

Страница 2: ...ANT450c ML 2103 TABLE OF CONTENTS PROGRAM START 3 PARAMETER SETTINGS 5 FACTORY SETTINGS DEFAULT 8 ERROR ALARMS AND TROUBLESHOOTING 8 INHALT PROGRAMMSTART 9 SOLLWERTEINGABE 11 WERKSEINSTELLUNGEN STANDA...

Страница 3: ...an internally calculated duty cycle LINE Pipe line temperature measurement Assignment of sensors Sensor 1 for heating circuit 1 sensor 2 for heating circuit 2 a revision of this assignment can be don...

Страница 4: ...CHEM 4 RAYCHEM OM EU1838 ELEXANT450c ML 2103 Main Screen SETTINGS KEYLOCK APPLICATION WARNINGS TIME SET TEMPERATURE HEATING ZONE 1 2 RELAY ON OFF SENSOR NUMBER OPERATION MODE ACTUAL TEMPERATURE APPLIC...

Страница 5: ...ey lock KeyLock Access code 3000 When key lock is On the setup and timer menus are protected by password The unit can be unlocked by entering the pre defined password 3000 After 10 minutes of inactivi...

Страница 6: ...Other system can be used if heating cable type is not known or listed Pipe diameter DN 25 DN 25 Range DN 10 DN 125 Default DN 25 Assign the correct pipe diameter per heating zone 1 and or 2 You can ch...

Страница 7: ...NO FI RU CZ PL SK LT Country Select a country in this menu Your selection defines the default values used for time format pipe diameter and insulation thickness and customer contact data Countries DE...

Страница 8: ...ound OFF Key lock ON ERROR ALARMS AND TROUBLESHOOTING Error Code Elexant 450C Remedy E 2 1 SENSOR_1_OPEN Check sensor connection E 2 2 SENSOR_1_SHORT Check sensor and replace it E 2 3 SENSOR_2_OPEN Ch...

Страница 9: ...nes definierten Arbeitszyklus zu betreiben ROHRF HLER Leitungsrohr Temperaturmessung F hlerzuordnung F hler 1 zu Heizkreis 1 F hler 2 zu Heizkreis 2 Die Zuordnung kann sp ter im Parametrierungsmen ge...

Страница 10: ...M 10 RAYCHEM OM EU1838 ELEXANT450c ML 2103 Hauptbildschirm EINSTELLUNGEN TASTEN SPERRE ANWENDUNG WARNUNGEN ZEIT SOLL TEMPERATUR HEIZZONE 1 2 RELAIS EIN AUS F HLERNUMMER BETRIEBSART AKTUELLE TEMPERATUR...

Страница 11: ...ugangscode 3000 Wenn die Tastensperre auf Ein steht sind die Men s Setup und Timer durch ein Passwort gesch tzt Das Ger t kann durch Eingabe des vordefinierten Passworts 3000 tempor r entsperrt werden...

Страница 12: ...ZH Heizbandreihe 10XL2 ZH 15XL2 ZH 26XL2 ZH 31XL2 ZH FS C10 2X Andere Systeme Standard W hlen Sie den Typ des in Ihrer Installation verwendeten nVent RAYCHEM Heizkabels das an Heizzone 2 angeschlossen...

Страница 13: ...ehler nicht ausgeschaltet Hysterese 2 K 2 K Bereich 1 5 Standard 2 K Hysteresewert kann oberhalb des Sollwerts ver ndert werden ALLGEMEINE EINSTELLUNGEN Sprache W hlen Sie Ihre Sprache aus dem Sprachm...

Страница 14: ...ARME UND FEHLERBEHEBUNG Fehlercode Elexant 450C Fehlerbehebung E 2 1 F hler 1 offen F hlerverbindung pr fen E 2 2 F hler 1 Kurzschluss F hler pr fen und austauschen E 2 3 F hler 2 offen F hlerverbindu...

Страница 15: ...605 01 88 salesee nVent com Italia Tel 39 02 577 61 51 Fax 39 02 577 61 55 28 salesit nVent com Lietuva Latvija Eesti Tel 370 5 2136633 Fax 370 5 2330084 info baltic nVent com Magyarorsz g Tel 36 1 25...

Отзывы: